{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED36-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED36-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED36-0AC0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 75.6 kA interrupting at 240 V, TM210 overcurrent release, 2 auxiliary switches HQ.","salesMarkdown":"The Siemens SENTRON 3VA1010-3ED36-0AC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. It carries a 75.6 kA interrupting rating at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — numbers that tell you where this breaker lives: it's sized for high-fault commercial and industrial distribution panels where the available short-circuit current is substantial. Rated insulation voltage Ui is 800 V, and the operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C. It ships with 2 auxiliary switches (HQ type) pre-installed, which is a time-saver on the panel build: no separate add-on order, no wiring guess on the aux contact block. The 100 A rating holds flat from 40 °C to 50 °C, then tapers: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, 90 A at 70 °C. The breaker body is 76.2 mm wide, 130 mm tall, and 70 mm deep, which is the standard SENTRON 3VA fixed-panel footprint.","metaTitle":"Siemens 3VA1010-3ED36-0AC0 SENTRON MCCB, 100 A, 3-Pole, 75.6","metaDescription":"Siemens SENTRON 3VA1010-3ED36-0AC0 molded case circuit breaker, 100 A rated continuous current, 3-pole, 75.6 kA interrupting at 240 V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=59477&mlfb=3VA1010-3ED36-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0AC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1010-3ED36-0AC0?","answer":"Submit an RFQ. We source these through the standard Siemens distribution channel and confirm pricing and availability at quote time — no stock count or price figure on this page."},{"question":"What is the closest functional second-source to 3VA1010-3ED36-0AC0?","answer":"The 3VA1010-2ED32-0JA0 is a close sibling in the same SENTRON 3VA family. Both are 3-pole, 100 A MCCBs with a TM release, but the -2ED32-0JA0 has a different interrupting rating and auxiliary contact configuration. The physical footprint is the same, so it drops into the same panel cutout, but verify the interrupting rating matches your fault study before swapping."},{"question":"What is 3VA1010-3ED36-0AC0's listed depth?","answer":"70 mm. That's the body depth from the mounting plane to the front cover — fits standard 200 mm deep enclosures with room for wiring."},{"question":"What is 3VA1010-3ED36-0AC0's listed width?","answer":"76.2 mm. That's the standard 3VA fixed-panel width; it fits the same DIN-rail or backplate footprint as other 3VA 3-pole breakers."},{"question":"Will 3VA1010-3ED36-0AC0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"Yes, the physical footprint is identical — same width, height, depth, and mounting pattern. The line and load lugs are in the same positions. The difference is in the interrupting rating and auxiliary contact count, so check the fault study and aux wiring before the swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED36-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}