{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED36-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED36-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED36-0CA0, molded case circuit breaker, 3-pole, 100 A, TM210 release, 75.6 kA at 240 V, undervoltage release, line protection.","salesMarkdown":"The Siemens SENTRON 3VA1010-3ED36-0CA0 is a 3-pole molded case circuit breaker rated for 100 A continuous at 40 °C, with a TM210 thermal-magnetic overcurrent release designed for line protection. The interrupting ratings climb to 75.6 kA at 240 V and 52.5 kA at 415 V, then taper to 7.5 kA at 690 V — so the available fault current at the panel's service voltage determines whether this breaker clears a short without upstream coordination issues. The undervoltage release (UVR) built into this order code means the breaker trips on loss of control voltage, a common requirement for emergency-stop or safety circuits where a drop-out must isolate the load. ## Thermal derating and enclosure planning The 100 A rating holds flat through 50 °C ambient, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. In a sealed panel with multiple breakers ganged, that curve determines the real load you can protect without nuisance tripping. Maximum power loss is 27.5 W, which factors into the enclosure's thermal budget when grouping several breakers in a confined space. The 130 mm height and 70 mm depth leave clearance for standard busbar connections and outgoing cable lugs. No communication module or ground-fault monitoring is integrated — this is a plain line-protection breaker with undervoltage release only. ## Environmental and compliance range No trip indicator or voltage-trigger accessory is fitted on this variant — the UVR is the only auxiliary release.","metaTitle":"Siemens 3VA1010-3ED36-0CA0 SENTRON MCCB, 100 A, 3-Pole, 75.6","metaDescription":"Siemens SENTRON 3VA1010-3ED36-0CA0 molded case circuit breaker, 100 A rated, 3-pole, 75.6 kA interrupting at 240 V. Current lifecycle. Quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"27.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10103ED360AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=25039&mlfb=3VA1010-3ED36-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0CA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1010-3ED36-0CA0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is 3VA1010-3ED36-0CA0's interrupting capacity at 240 V?","answer":"75.6 kA at 240 V, with 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, the 3VA1010-3ED36-0CA0 includes an undervoltage release (UVR) as the auxiliary release, designed to trip the breaker on loss of control voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED36-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}