{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED36-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED36-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED36-0CH0, molded case circuit breaker, 3-pole, 100 A (Iu), line protection, TM210 thermal-magnetic release, 75.6 kA breaking capacity at 240 V.","salesMarkdown":"## MCCB for line protection — 100 A continuous, TM210 release The 3-pole design fits three-phase distribution panels where the neutral is protected separately or not at all. Breaking capacity is specified at four voltage levels: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. For a 415 V distribution board — common in European industrial plants — the 52.5 kA figure gives substantial headroom above the typical 25–36 kA prospective fault level, so selectivity with downstream MCBs is achievable without a current-limiting upstream breaker. Thermal derating is published across the full operating range: the breaker holds 100 A from 40 °C through 50 °C, then steps down to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. If the panel ambient sits at 55 °C — not unusual in a sealed enclosure near process heat — the usable rating drops to 96 A, so the feeder should be loaded to that figure, not the nameplate 100 A. ## Integrated undervoltage release and auxiliary contacts The integrated auxiliary trip order code is 3VA9608-0BB24 — relevant if you need a replacement or spare for the internal shunt trip assembly. ## Active production — no lifecycle concern The lifecycle stage is listed as current, meaning Siemens continues to manufacture this order code without a phase-out notice. For a BOM line that needs repeatability across builds, this is the straightforward choice — no last-time-buy clock, no successor cross-reference to manage. ## Envelope and panel fit The 76.2 mm width is a standard 3-pole MCCB footprint — three 25.4 mm (1-inch) pole spacings — so it drops into existing panel cutouts and busbar systems designed for that pitch.","metaTitle":"Siemens 3VA1010-3ED36-0CH0 SENTRON MCCB, 100 A, 3-Pole, Line","metaDescription":"Siemens 3VA1010-3ED36-0CH0 SENTRON MCCB, 100 A rated at 40 °C, 3-pole, TM210 release, 75.6 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=516427&mlfb=3VA1010-3ED36-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0CH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1010-3ED36-0CH0 at 415 V?","answer":"52.5 kA at 415 V. At 240 V it is 75.6 kA, at 440 V it is 32 kA, and at 690 V it is 7.5 kA."},{"question":"What does the TM210 release mean on this MCCB?","answer":"TM210 is a thermal-magnetic overcurrent release — the thermal element handles overload protection (inverse-time curve), and the magnetic element handles short-circuit protection (instantaneous). It is the standard release for line protection."},{"question":"Will 3VA1010-3ED36-0CH0 drop into a panel specified for 3VA1010-4ED36-0CC0?","answer":"The envelope dimensions are identical — 130 mm height, 76.2 mm width, 70 mm depth — and both are 3-pole SENTRON MCCBs, so the mechanical fit is the same. The difference is in the release and accessories: this unit has a TM210 release and an undervoltage release, while the -4ED36-0CC0 variant uses a different release configuration. Verify the protection settings match your coordination study before substituting."},{"question":"Where can I buy 3VA1010-3ED36-0CH0 and how is it quoted?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED36-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}