{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED36-0JA0, 3-pole molded case circuit breaker, 100 A at 40 °C, 75.6 kA at 240 V, shunt trip (STL), TM210 overcurrent release.","salesMarkdown":"The Siemens SENTRON 3VA1010-3ED36-0JA0 is a 3-pole molded case circuit breaker rated 100 A at 40 °C, with a breaking capacity of 75.6 kA at 240 V — enough headroom for high-fault utility feeds or transformer secondaries where the available short-circuit current is substantial. ## Integration notes The 3VA1010-3ED36-0JA0 occupies 70 mm depth, 76.2 mm width, and 130 mm height — standard panel footprint for a 3-pole MCCB in this class. The shunt trip (STL) auxiliary release means you can wire an emergency-stop or undervoltage coil into the breaker without adding an external contactor. ## Thermal derating Rated 100 A continuous at 40 °C, and it holds that rating through 50 °C. Above 55 °C it derates: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C.","metaTitle":"Siemens SENTRON 3VA1010-3ED36-0JA0 MCCB, 100 A, 75.6 kA","metaDescription":"Siemens SENTRON 3VA1010-3ED36-0JA0 molded case circuit breaker, 3-pole, 100 A at 40 °C, 75.6 kA at 240 V, shunt trip (STL), TM210 release. Active lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10103ED360AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=366064&mlfb=3VA1010-3ED36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA1010-3ED36-0JA0 and how is it quoted?","answer":"This breaker is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — quantities and lead time are confirmed per request."},{"question":"What is the closest functional second-source to 3VA1010-3ED36-0JA0?","answer":"The 3VA1010-2ED32-0JA0 is a direct sibling in the same SENTRON 3VA family. The key difference is the overcurrent release: the -3ED36 carries a TM210, while the -2ED32 uses a different TM release. Both share the same 3-pole frame, 100 A rating, and shunt trip option, so they drop into the same panel footprint without rewiring."},{"question":"What is the depth of 3VA1010-3ED36-0JA0?","answer":"70 mm (2.76 in)."},{"question":"What is the width of 3VA1010-3ED36-0JA0?","answer":"76.2 mm (3 in)."},{"question":"Will 3VA1010-3ED36-0JA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"Yes — both breakers share the same 3-pole frame dimensions (70 mm depth, 76.2 mm width, 130 mm height) and the same SENTRON mounting pattern. The shunt trip (STL) wiring is identical. The only difference is the overcurrent release curve (TM210 vs TM on the -2ED32), so verify coordination if selectivity studies were done, but the physical swap is straightforward."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}