{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED36-0JC0, molded case circuit breaker, 3-pole, 100 A rated continuous current, TM210 thermal-magnetic release, line protection version, 75.6 kA breaking capacity at 240 V.","salesMarkdown":"Breaking capacity is voltage-dependent: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. At 415 V — the common European three-phase distribution voltage — the 52.5 kA figure gives substantial fault-current headroom for most industrial service-entrance and sub-distribution applications. ## Thermal derating and real-world loading Above that it derates: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. ## Auxiliaries and integrated trip options This MCCB ships with two HQ auxiliary switches (form C) for status feedback — open/closed indication to a PLC or remote annunciator. The integrated auxiliary trip is order code 3VA9688-0BL32. Dimensions: 76.2 mm wide (roughly 3 inches — three 1-inch pole spaces), 130 mm tall, 70 mm deep.","metaTitle":"Siemens 3VA1010-3ED36-0JC0 SENTRON MCCB, 100 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1010-3ED36-0JC0 SENTRON molded case circuit breaker, 100 A rated, 3-pole, TM210 release, 75.6 kA at 240 V. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=464973&mlfb=3VA1010-3ED36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED36-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-3ED36-0JC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Send an RFQ with your quantity and target delivery window; availability and current pricing are confirmed at quote time."},{"question":"Will 3VA1010-3ED36-0JC0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"Both are 3-pole, 100 A SENTRON MCCBs on the same 3VA1 platform with identical dimensions (76.2 mm wide, 130 mm tall, 70 mm deep) and the same TM210 release family, so the mechanical footprint and bus-bar spacing match. The 3ED36-0JC0 adds a shunt trip and two HQ auxiliary switches that the 2ED32-0JA0 may lack — if the original panel wiring already connects those auxiliaries, the drop-in works; if the panel has no shunt-trip wiring, the extra terminal is simply unused."},{"question":"What compliance documentation does this brand provide for 3VA1010-3ED36-0JC0 (RoHS, REACH, UL, IEC)?","answer":"Siemens SENTRON MCCBs carry IEC 60947-2 certification as standard. RoHS and REACH declarations are available from Siemens' documentation portal for the 3VA1 series. UL/CSA listings depend on the specific variant; the 3VA1 platform is designed to meet UL 489, but verify the exact listing mark on the nameplate for your jurisdiction."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}