{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-4ED32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-4ED32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-4ED32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-4ED32-0JC0, 3-pole molded case circuit breaker, 100 A rated at 40 °C, 121 kA breaking capacity at 240 V AC, line protection design with shunt trip and auxiliary switches.","salesMarkdown":"## Siemens 3VA1010-4ED32-0JC0 — 100 A SENTRON MCCB, Line Protection with Shunt Trip Per the specification, the interrupting capacity is rated at 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. Derating begins at 55 °C (98 A), stepping down to 91 A at 70 °C. Maximum power loss is 25 W, which should be factored into enclosure thermal calculations, particularly in densely packed panels. ## Physical Dimensions and Panel Fit The 3VA1010-4ED32-0JC0 occupies a 76.2 mm width (3 in), 130 mm height (5.12 in), and 70 mm depth (2.76 in). These dimensions match the standard SENTRON 3VA1 frame footprint, so a panel originally laid out for a 3VA1110-series MCCB will accept this unit without bus-bar or mounting-plate modifications. The 3-pole construction fits directly onto the DIN rail or mounting plate per the manufacturer's installation instructions.","metaTitle":"Siemens 3VA1010-4ED32-0JC0 SENTRON MCCB, 100A, 121kA at 240V","metaDescription":"Siemens 3VA1010-4ED32-0JC0 SENTRON molded case circuit breaker, 3-pole, 100A rated at 40°C, 121kA breaking capacity at 240V AC. Active production. Quoted to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10104ED320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=502787&mlfb=3VA1010-4ED32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1010-4ED32-0JC0 at 240 V?","answer":"The interrupting capacity is 121 kA at 240 V AC. At 415 V it is 75.6 kA, at 440 V it is 52.5 kA, and at 500 V and 690 V it is 11.9 kA."},{"question":"Will 3VA1010-4ED32-0JC0 drop into a panel specified around 3VA1110-5EE32-0LC0 without rewiring?","answer":"Yes. Both units share the same SENTRON 3VA1 frame footprint (76.2 mm width, 130 mm height, 70 mm depth) and 3-pole construction, so the physical mounting and bus-bar positions are identical. No rewiring of the panel layout is required for the swap."},{"question":"Where can I buy 3VA1010-4ED32-0JC0?","answer":"This MCCB is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at the time of quotation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-4ED32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-4ED32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}