{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-4ED36-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-4ED36-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-4ED36-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED36-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-4ED36-0AF0, molded case circuit breaker, 3-pole, 100 A, 121 kA at 240 V, line protection, TM210 release, 70 mm depth, 76.2 mm width, 130 mm height.","salesMarkdown":"The interrupting ratings climb steeply as voltage drops: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That spread tells you it's built for high-fault-capacity main or subfeed applications where you need selectivity with downstream breakers. Above that it derates: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 25 W — that's the heat you need to vent inside the enclosure if the breaker is fully loaded. The TM210 release is the thermal-magnetic type, so no electronic adjustment; the trip curve is fixed by the thermal element and magnetic pickup. The breaker measures 70 mm deep, 76.2 mm wide, and 130 mm tall — that's roughly 2.76 by 3 by 5.12 inches (–). No undervoltage release, no voltage trigger, no ground-fault monitoring, and no communication function — this is a plain-vanilla thermal-magnetic MCCB for straightforward line protection.","metaTitle":"Siemens 3VA1010-4ED36-0AF0 SENTRON MCCB, 100 A, 3-Pole, 121","metaDescription":"Siemens SENTRON 3VA1010-4ED36-0AF0 molded case circuit breaker, 100 A, 3-pole, 121 kA at 240 V. Line protection, TM210 release. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10104ED360AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=286217&mlfb=3VA1010-4ED36-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED36-0AF0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1010-4ED36-0AF0?","answer":"Submit an RFQ against this order code. Availability and current pricing are confirmed at quote time through independent distribution — no stock count or price figure is published here."},{"question":"When sourcing 3VA1010-4ED36-0AF0, what's the closest functional second-source — 3VA1110-5ED36-0AC0?","answer":"The 3VA1110-5ED36-0AC0 is a peer in the same SENTRON 3VA family but carries a different frame size and interrupting rating. Verify the panel cutout and short-circuit requirements before substituting — the 3VA1010-4ED36-0AF0 is the 100 A, 3-pole, high-interrupt version with a TM210 release, while the 3VA1110 variant may have a different trip unit or SCCR."},{"question":"What is 3VA1010-4ED36-0AF0's listed depth (70 mm) on this component line?","answer":"The depth is 70 mm, which is 2.76 inches. That's the dimension from the mounting surface to the front of the breaker body — factor in handle throw and wiring space when sizing the enclosure."},{"question":"What is 3VA1010-4ED36-0AF0's listed width (76.2 mm) on this component line?","answer":"The width is 76.2 mm, or 3 inches. That's the standard 3-pole MCCB footprint for the SENTRON 3VA frame — it fits the same DIN-rail or panel-mount spacing as other 3VA three-pole units."},{"question":"Will 3VA1010-4ED36-0AF0 drop into a panel that was specified around 3VA1110-5ED36-0AC0 without rewiring?","answer":"Not without checking. The 3VA1110-5ED36-0AC0 is a different frame size within the SENTRON 3VA family; the mounting hole pattern, bus-bar spacing, and terminal layout may differ. Compare the dimensional drawings and terminal specifications before assuming a direct swap."},{"question":"What compliance documentation does this brand provide for 3VA1010-4ED36-0AF0 (RoHS, REACH, UL, IEC)?","answer":"Siemens SENTRON MCCBs are typically supplied with RoHS, REACH, UL, and IEC declarations. For the exact certificate matching this order code, request it with your RFQ — the documentation is available from the manufacturer or through the supply channel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-4ED36-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-4ED36-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}