{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-4ED36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-4ED36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-4ED36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, Molded case circuit breaker, 3VA1010-4ED36-0JA0, 3-pole, 100 A, TM210 thermal-magnetic release, line protection, 121 kA at 240 V.","salesMarkdown":"The 3VA1010-4ED36-0JA0: The TM210 release combines a thermal bimetal for overload protection and a magnetic coil for short-circuit protection, sized for general distribution and motor branch-circuit duty where adjustable thermal pickup is not required. Rated insulation voltage is 800 V, so the breaker is suitable for 480/277 V and 600 V panelboards with adequate clearance — the 800 V Ui covers most North American and IEC low-voltage installations. This MCCB delivers 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. At 415 V the 75.6 kA rating covers most European industrial distribution panels where the prospective short-circuit current at the main switchboard is typically 50–65 kA — this breaker provides headroom above that common threshold. ## Thermal derating — real-world current capacity at elevated panel temperatures Above that it derates: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. The 76.2 mm width is a standard 3-pole MCCB footprint (roughly 3 inches), so it fits existing SENTRON 3VA panel cutouts and busbar risers without adapter plates. No IP rating on the rear or sides; the breaker relies on the enclosure for overall ingress protection. ## Accessory and release configuration The integrated auxiliary trip accessory is order code 3VA9688-0BL32 — order it alongside if you need remote-trip indication or a separate control circuit. No communication function, no phase-failure detection, and no ground-fault monitoring are built in. This is a plain line-protection MCCB — if you need those features, look at the 3VA1 with electronic releases or the 3VA2 series with communication modules.","metaTitle":"Siemens 3VA1010-4ED36-0JA0 SENTRON MCCB, 100 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA1010-4ED36-0JA0 molded case circuit breaker, 100 A rated continuous current, 3-pole, TM210 release, 121 kA at 240 V. Current production. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=165431&mlfb=3VA1010-4ED36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1010-4ED36-0JA0 at 240 V and 415 V?","answer":"121 kA at 240 V and 75.6 kA at 415 V, with 52.5 kA at 440 V and 11.9 kA at 690 V."},{"question":"What does the TM210 release designation mean?","answer":"TM210 is a thermal-magnetic fixed-release with a 100 A continuous-current rating — the '210' indicates the release family and amp rating. It provides overload protection via bimetal and short-circuit protection via magnetic coil, non-adjustable."},{"question":"Does this MCCB include an undervoltage release or auxiliary contacts?","answer":"No. It ships without undervoltage release and without auxiliary contacts. It does include a shunt trip release (STL) for remote tripping; the integrated auxiliary trip accessory is order code 3VA9688-0BL32."},{"question":"Where can I buy 3VA1010-4ED36-0JA0 and get current pricing?","answer":"This part is sourced to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-4ED36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-4ED36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}