{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-4ED36-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-4ED36-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-4ED36-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED36-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-4ED36-0KA0, molded case circuit breaker, 3-pole, 100 A, line protection, TM210 release, 70 mm depth, 76.2 mm width, 130 mm height.","salesMarkdown":"The 3VA1010-4ED36-0KA0: Breaking capacity is the headline here: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — a standard 3-pole MCCB footprint that drops into SENTRON panelboards and most DIN-rail adapter kits. At 55 °C it drops to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A. If your panel ambient sits above 50 °C, size the load side accordingly or bump to the next frame. ## Auxiliary releases and connectivity Voltage trigger is present, so it responds to a separate control voltage rather than a mechanical latch. Current production — no LTB or phase-out on this code. That means it's still a standard catalog item, not a surplus gamble. If you're freezing a BOM for a multi-panel run, this one won't trigger a last-time-buy scramble.","metaTitle":"Siemens 3VA1010-4ED36-0KA0 SENTRON MCCB, 100A, 3-Pole, 70mm","metaDescription":"Siemens SENTRON 3VA1010-4ED36-0KA0 molded case circuit breaker, 100A continuous, 3-pole, breaking capacity 121kA at 240V. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=122457&mlfb=3VA1010-4ED36-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED36-0KA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-4ED36-0KA0 and get a price?","answer":"We source it to order against an RFQ. Submit a quote request through the storefront; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1010-4ED36-0KA0 at 415 V?","answer":"75.6 kA at 415 V, which covers most European industrial distribution panels. At 240 V it's 121 kA, at 440 V it's 52.5 kA, and at 690 V it's 11.9 kA."},{"question":"Does 3VA1010-4ED36-0KA0 include a shunt trip?","answer":"Yes, it ships with a shunt trip (STL) auxiliary release, part number 3VA9688-0BL33 for the integrated trip unit. No undervoltage release or auxiliary contacts are included on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-4ED36-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-4ED36-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}