{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-4ED42-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-4ED42-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-4ED42-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED42-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-4ED42-0DA0, molded case circuit breaker, 4-pole, 100 A (40 °C), TM210 thermal-magnetic overcurrent release, line protection, with undervoltage release, 70 mm depth.","salesMarkdown":"This MCCB delivers 121 kA interrupting capacity at 240 V, dropping to 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. Those figures cover most industrial service-entrance and sub-distribution fault levels; the 690 V rating is useful for 600 V class Canadian or mining installations where the full kA is still needed. The 800 V rated insulation voltage (Ui) supports use in 690 V systems with margin, and the 100 A frame at 40 °C holds flat through 50 °C — no derating needed up to that point. Above 55 °C it steps down to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Dimensions are 130 mm height, 101.6 mm width, and 70 mm depth — a compact 4-pole footprint that fits standard MCCB mounting plates in SENTRON distribution boards. The 27.5 W maximum power loss should be factored into enclosure thermal calculations, especially in sealed or high-ambient cabinets. No communication module or ground-fault monitoring is fitted on this variant; the UVR is the only auxiliary release.","metaTitle":"Siemens 3VA1010-4ED42-0DA0 SENTRON MCCB, 100A, 4-Pole, TM210","metaDescription":"Siemens 3VA1010-4ED42-0DA0 SENTRON molded case circuit breaker, 100A at 40°C, 4-pole, TM210 thermal-magnetic trip, 121kA at 240V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"27.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10104ED420AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=487005&mlfb=3VA1010-4ED42-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-4ED42-0DA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1010-4ED42-0DA0 at 415 V?","answer":"At 415 V the interrupting capacity is 75.6 kA."},{"question":"Where can I buy 3VA1010-4ED42-0DA0 and how is it quoted?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"Will 3VA1010-4ED42-0DA0 drop into a panel specified around 3VA1010-3ED36-0AA0 without rewiring?","answer":"Both are 4-pole SENTRON 3VA frame breakers with the same mounting footprint, so mechanical fit is identical. The difference is in the trip unit and rating — this one carries a TM210 with 100 A at 40 °C versus the 3ED36 variant's different thermal-magnetic curve. No rewiring needed for the same buswork, but verify the trip coordination study if replacing one with the other."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-4ED42-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-4ED42-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}