{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1025-2ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1025-2ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1025-2ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1025-2ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1025-2ED32-0AA0, 3-pole molded case circuit breaker, 25 A (40 °C), breaking capacity 52.5 kA at 240 V, TM210 release, line protection design.","salesMarkdown":"## What it is and what it does The Siemens 3VA1025-2ED32-0AA0 is a 3-pole molded case circuit breaker (MCCB) from the SENTRON series, designed for line protection — meaning it protects cables and distribution buswork against overload and short-circuit, not motor or generator circuits. Rated 25 A at 40 °C (continuous current holds flat through 50 °C, then derates to 23 A at 70 °C), with a breaking capacity of 52.5 kA at 240 V AC and 32 kA at 415 V AC — enough for most industrial distribution panels fed by a transformer in the 500–1000 kVA range. The overcurrent release is a TM210 thermal-magnetic type — fixed thermal and magnetic trip settings, no electronic adjustment. That keeps the part simple and reliable for standard feeder protection, but means you cannot dial in a different trip curve on site. ## Breaking capacity across voltages — what it means for your panel At 440 V the breaker interrupts 13.6 kA; at 500 V and 690 V it drops to 7.5 kA. If your system fault current at the panel exceeds those numbers at the operating voltage, you need a higher-rated MCCB upstream or a current-limiting fuse ahead of this breaker. Rated insulation voltage is 800 V, so the breaker itself can be used in 690 V systems — the lower interrupting capacity at that voltage is the limiting factor, not the insulation. ## Physical fit and panel integration Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that fits most Siemens SENTRON distribution panels and many third-party enclosures with a 3 x 76.2 mm cutout. The front face carries IP40 protection (no water jets, but solid objects larger than 1 mm are kept out). No undervoltage release, no shunt trip, no communication module — this is a bare thermal-magnetic breaker. If you need remote tripping or status feedback, you will need to add accessories or pick a different variant. ## Lifecycle and sourcing reality Maximum power loss is 8.5 W — negligible for thermal budgeting in a panel, but worth noting if you are packing many breakers in a sealed enclosure without forced ventilation.","metaTitle":"Siemens 3VA1025-2ED32-0AA0 SENTRON MCCB, 25 A, 52.5 kA","metaDescription":"Siemens SENTRON 3VA1025-2ED32-0AA0 molded case circuit breaker, 3-pole, 25 A rated at 40 °C, breaking capacity 52.5 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"3","Width":"76.2 mm","Height":"130 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b1fa333d01c54467cf658cf7b8f156d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=430711&mlfb=3VA1025-2ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1025-2ED32-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1025-2ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1025-2ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}