{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1025-2ED32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1025-2ED32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1025-2ED32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1025-2ED32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1025-2ED32-0HA0, 3-pole molded case circuit breaker, 25 A rated continuous current at 40 °C, TM210 thermal-magnetic release, shunt trip (STL), interrupting ratings 52.5 kA at 240 V / 32 kA at 415 V / 13.6 kA at 440 V / 7.5 kA at 690 V.","salesMarkdown":"Its interrupting capacity hits 52.5 kA at 240 V and 32 kA at 415 V — figures that govern fault-clearing in low-voltage distribution panels where available fault current runs high. Compared to the lower-rated 3VA1010-2ED32-0JA0 (10 A frame), this 25 A version shares the same 76.2 mm width and 130 mm height but carries a higher continuous rating and correspondingly higher interrupting duty at each voltage point. Both use the TM210 release family and accept the same 3VA9688-0BL30 integrated auxiliary trip. Panel cutout and busbar spacing are identical, so a swap between the two requires no enclosure modification — only verifying that the downstream load and fault current are within the 25 A frame's limits. The 70 mm depth fits standard 200 mm deep enclosures; the 76.2 mm width (roughly 3 module spaces) leaves room for adjacent breakers or accessories in a multi-pole lineup.","metaTitle":"Siemens 3VA1025-2ED32-0HA0 SENTRON MCCB, 25 A, 52.5 kA at 24","metaDescription":"Siemens 3VA1025-2ED32-0HA0 SENTRON molded case circuit breaker, 25 A rated continuous current, 52.5 kA interrupting at 240 V. Active production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"24 A","at 60 °C":"23.5 A","at 65 °C":"23 A","at 70 °C":"22.5 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"25 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"25 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"25 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=433576&mlfb=3VA1025-2ED32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1025-2ED32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1025-2ED32-0HA0 at different voltages?","answer":"The breaker delivers 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. These ratings determine where it can be applied in the distribution hierarchy — the 52.5 kA figure suits main or feeder positions with high available fault current."},{"question":"What is the closest functional second-source for 3VA1025-2ED32-0HA0?","answer":"The 3VA1010-2ED32-0JA0 is the nearest functional sibling — same 3-pole frame, same TM210 release, same physical footprint (76.2 mm width, 130 mm height, 70 mm depth). The difference is the continuous current rating: 10 A vs 25 A. A direct swap into the same panel cutout is possible if the load current and interrupting requirements fit the 10 A frame."},{"question":"Where can I buy 3VA1025-2ED32-0HA0?","answer":"This part is sourced and quoted to order through independent industrial distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does this brand provide for 3VA1025-2ED32-0HA0?","answer":"Siemens provides the device manual (covering DC network application notes under the 3VA molded case circuit breaker manual), plus the standard CE declaration of conformity and manufacturer's declaration for RoHS/REACH compliance. The reference code per DIN EN 81346-2 is Q."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1025-2ED32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1025-2ED32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}