{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1025-2ED32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1025-2ED32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1025-2ED32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1025-2ED32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1025-2ED32-0JH0, molded case circuit breaker, 3-pole, 25 A, TM210 thermal-magnetic release, line protection, with shunt trip (STL) and 2 aux + 1 alarm switch, 70 mm depth.","salesMarkdown":"## SENTRON 3VA1025-2ED32-0JH0 — integrator's terse spec recap Breaking capacity is rated per voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. That 52.5 kA at 240 V is high for a 25 A frame — it handles heavy fault current on a 240 V secondary without upstream coordination headaches. This is the workhorse choice for standard motor branch circuits and distribution panels where you don't need the selectivity tuning of an electronic ETU. The 3-pole unit is 76.2 mm wide, 130 mm tall, and 70 mm deep — fits a standard MCCB slot in most Siemens panelboards. ## Auxiliary and trip configuration — what ships on this variant The integrated shunt trip part number is 3VA9688-0BL32 — useful for spares ordering. If you need undervoltage release or Modbus, this is not the right variant; look at the 3VA2 family with electronic releases. Mechanical endurance is 15,000 operations (latching type). No official successor exists because the part is current. If you need a functional cross-reference within the same SENTRON 3VA family, the closest peers are 3VA1010-2ED42-0AE0 (10 A frame, different trip and aux config) and 3VA1020-3ED36-0AA0 (20 A, 3-pole, different release) — but the 3VA1025-2ED32-0JH0 is the 25 A variant with the specific shunt trip and HQ aux switch combination. Panel footprint is the same 3-pole 70 mm depth across the 3VA1/2 series, so a drop-in replacement for a panel originally specced around a 3VA1010-2ED42-0AE0 would only work if the amp rating matches the load — you cannot simply swap a 10 A for a 25 A without checking the branch circuit protection. ## Panel integration — what to know before the wire hits the lug The TM210 release is non-interchangeable — the trip unit is integral to the breaker. If you need field-adjustable thermal or magnetic settings, you are looking at the 3VA2 electronic-trip family. For a fixed 25 A branch circuit with shunt trip and remote status (2 aux + 1 alarm), this variant is the correct pick.","metaTitle":"Siemens 3VA1025-2ED32-0JH0 SENTRON MCCB, 25 A, 3-Pole, TM210","metaDescription":"Siemens 3VA1025-2ED32-0JH0 SENTRON molded case circuit breaker, 25 A rated, 3-pole, TM210 release. Breaking capacity 52.5 kA at 240 V. Active production. Quoted to order against RF","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"24 A","at 60 °C":"23.5 A","at 65 °C":"23 A","at 70 °C":"22.5 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"25 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"25 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"25 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=509949&mlfb=3VA1025-2ED32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1025-2ED32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA1025-2ED32-0JH0 and how is it quoted for volume purchases?","answer":"The 3VA1025-2ED32-0JH0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for firm pricing and lead time on volume."},{"question":"What is the closest functional second-source to 3VA1025-2ED32-0JH0?","answer":"Within the SENTRON 3VA family, the closest peers are 3VA1010-2ED42-0AE0 (10 A frame) and 3VA1020-3ED36-0AA0 (20 A frame), but neither is a direct replacement — the 3VA1025-2ED32-0JH0 is the 25 A variant with the specific shunt trip and HQ auxiliary switch combination. Panel footprint (3-pole, 70 mm deep) is shared, so mechanical fit is the same, but amp rating must match the branch circuit."},{"question":"What is the depth of 3VA1025-2ED32-0JH0?","answer":"The 3VA1025-2ED32-0JH0 has a depth of 70 mm, width of 76.2 mm, and height of 130 mm."},{"question":"What compliance documentation does the SENTRON 3VA series carry?","answer":"The SENTRON 3VA series carries IEC/EN 60947-2 certification for MCCBs. The specific order code 3VA1025-2ED32-0JH0 is a line protection device with IP40 front protection, reference code Q per DIN EN 81346-2. For specific RoHS/REACH/UL declarations, refer to the Siemens declaration of conformity for the 3VA family — the evidence does not list individual cert numbers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1025-2ED32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1025-2ED32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}