{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1025-3ED32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1025-3ED32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1025-3ED32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1025-3ED32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1025-3ED32-0HH0, molded case circuit breaker, 3-pole, 25 A, TM210 thermal-magnetic release, 75.6 kA at 240 V, shunt trip, 2 aux + 1 alarm switch.","salesMarkdown":"## Line protection MCCB — 25 A, 3-pole, TM210 release The Siemens SENTRON 3VA1025-3ED32-0HH0 is a 3-pole molded case circuit breaker rated for 25 A continuous current (Iu) at 40 °C, with a TM210 thermal-magnetic overcurrent release. It carries a 75.6 kA interrupting rating at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — the SCCR drops as voltage rises, so verify the available fault current at your system voltage. The TM210 release is fixed thermal and magnetic; no adjustment dial, so coordination studies should use the published trip curves. Built-in auxiliary contacts are 2 form-C aux switches plus 1 separate trip-alarm switch (HQ type), giving three independent signal paths for remote status and fault annunciation. The shunt trip release (STL) is factory-integrated — order code 3VA9688-0BL30 for the release module itself if you need a spare. Above that, derate linearly: 24 A at 55 °C, 23.5 A at 60 °C, 23 A at 65 °C, 22.5 A at 70 °C. The 70 mm depth and 76.2 mm width fit standard SENTRON 3VA panel cutouts; the 130 mm height leaves clearance for the shunt trip and auxiliary wiring.","metaTitle":"Siemens 3VA1025-3ED32-0HH0 SENTRON MCCB, 25 A, 3-Pole, 75.6","metaDescription":"Siemens SENTRON 3VA1025-3ED32-0HH0 molded case circuit breaker, 25 A, 3-pole, 75.6 kA interrupting at 240 V. TM210 release, shunt trip, 2 aux + 1 alarm. Current production. RFQ for","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"25 A","at 45 °C":"25 A","at 50 °C":"25 A","at 55 °C":"24 A","at 60 °C":"23.5 A","at 65 °C":"23 A","at 70 °C":"22.5 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"25 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"25 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"25 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=276527&mlfb=3VA1025-3ED32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1025-3ED32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA1025-3ED32-0HH0 at 415 V?","answer":"52.5 kA at 415 V. At 240 V it is 75.6 kA, at 440 V it drops to 32 kA, and at 690 V it is 7.5 kA."},{"question":"Does 3VA1025-3ED32-0HH0 include a shunt trip?","answer":"Yes, it has a factory-integrated shunt trip release (STL). The auxiliary release design is shunt trip, and the integrated auxiliary trip module order code is 3VA9688-0BL30."},{"question":"Where can I buy 3VA1025-3ED32-0HH0?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1025-3ED32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1025-3ED32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}