{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-2ED32-0AD0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-2ED32-0AD0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-2ED32-0AD0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED32-0AD0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-2ED32-0AD0, 3-pole molded case circuit breaker, 32 A at 40 °C, TM210 thermal-magnetic release, line protection, 52.5 kA breaking at 240 V.","salesMarkdown":"It carries a TM210 thermal-magnetic release, so the thermal element handles sustained overloads and the magnetic element clears high-fault events fast. Rated 32 A continuous at 40 °C ambient, with no derating needed up to 50 °C — still 32 A at 50 °C — then drops to 31 A at 55 °C and 30 A at 70 °C. That thermal stability is useful in a crowded enclosure where ambient heat builds. Breaking capacity is the headline number for an MCCB: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. If you need those options, you'd step to a different suffix. That simplifies ordering but means if your load draws 30 A continuous in a 55 °C panel, the breaker still holds at 31 A, so no nuisance tripping from ambient heat alone. At 415 V, the 32 kA interrupting rating covers most industrial 400 V distribution boards where the transformer impedance keeps fault levels under that threshold. Power loss is listed at 10.6 W maximum — that's the heat dissipated inside the enclosure at rated current. In a sealed panel with multiple breakers, that number feeds into the thermal budget for the cabinet cooling calculation.","metaTitle":"Siemens 3VA1032-2ED32-0AD0 SENTRON MCCB, 32 A, 3-Pole, TM210","metaDescription":"Siemens 3VA1032-2ED32-0AD0 SENTRON molded case circuit breaker, 32 A at 40 °C, 3-pole, TM210 thermal-magnetic release, breaking capacity 52.5 kA at 240 V. Current lifecycle. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1032-2ED32-0AD0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 100 breaking capacity class B Icu=16kA @ 415V 3-pole, line protection TM210, FTFM, In=32A overload protection Ir=32A fixed short-circuit protection Ii=10 x In nut keeper kit 3 auxiliary switches HQ","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10322ED320AA0","Design Of The Auxiliary Switch":"3 auxiliary switches HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/19166a03d9f39a26be07332d639043aa.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=182098&mlfb=3VA1032-2ED32-0AD0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1032-2ED32-0AD0?","answer":"Submit an RFQ through the storefront — this part is sourced to order through independent distribution, and current pricing and lead time are confirmed at quote time."},{"question":"Will 3VA1032-2ED32-0AD0 drop into a panel specified around 3VA1010-2ED32-0AD0?","answer":"Both are 3-pole SENTRON 3VA frame breakers with the same height (130 mm), width (76.2 mm), and depth (70 mm), so the physical footprint and panel cutout are identical. The difference is the current rating — 32 A on this unit versus 10 A on the 3VA1010 — and the TM210 release versus whatever release the 3VA1010 carries. No rewiring needed if the bus bars and lug sizes match the higher current."},{"question":"What compliance documentation does this brand provide for 3VA1032-2ED32-0AD0?","answer":"As a Siemens SENTRON MCCB, it carries the standard IEC 60947-2 certification for molded case circuit breakers. The manufacturer provides RoHS and REACH declarations as part of the product documentation package."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-2ED32-0AD0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-2ED32-0AD0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}