{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-2ED32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-2ED32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-2ED32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-2ED32-0BA0, 3-pole molded case circuit breaker, 32 A rated continuous current, TM210 thermal-magnetic release, 52.5 kA breaking capacity at 240 V, 70 mm depth.","salesMarkdown":"The Siemens 3VA1032-2ED32-0BA0 is a SENTRON 3-pole molded case circuit breaker (MCCB) rated for 32 A continuous current at 40 °C, with a TM210 thermal-magnetic release. It carries a 52.5 kA interrupting capacity at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — the breaking curve you need to match against the available fault current at the panelboard. An undervoltage release (UVR) is fitted as standard, so verify your control voltage matches the release coil rating before energizing. Derating is minimal up to 50 °C — still 32 A. At 55 °C it drops to 30.72 A, at 60 °C to 30.08 A, at 65 °C to 29.44 A, and at 70 °C to 28.8 A.","metaTitle":"Siemens 3VA1032-2ED32-0BA0 SENTRON MCCB, 32 A, 3-Pole, 52.5","metaDescription":"Siemens SENTRON 3VA1032-2ED32-0BA0 molded case circuit breaker, 32 A continuous, 3-pole, TM210 release, 52.5 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"32 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=139537&mlfb=3VA1032-2ED32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1032-2ED32-0BA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional alternative to 3VA1032-2ED32-0BA0?","answer":"The 3VA1010-2ED42-0AE0 is a sibling in the same SENTRON 3VA family, but it carries a 10 A frame rating versus the 32 A of this part. They share the same 3-pole form factor and TM release architecture, so a panel laid out for one can accept the other without rewiring — provided the load current and interrupting capacity requirements match the alternative's ratings."},{"question":"What compliance documentation does this breaker carry?","answer":"The SENTRON 3VA series is designed to meet IEC 60947-2 and UL 489 standards for molded case circuit breakers. Specific RoHS, REACH, and CE declarations are available from Siemens documentation for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-2ED32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-2ED32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}