{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-2ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-2ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-2ED36-0AA0, molded case circuit breaker, 3-pole, 32 A, TM210 thermal-magnetic release, line protection, 52.5 kA at 240 V, IP40 front.","salesMarkdown":"Its interrupting capacity hits 52.5 kA at 240 V AC and 32 kA at 415 V AC — enough to handle high-fault utility feeds or transformer secondaries without cascading upstream. At 55 °C it drops to 31 A, and at 70 °C it's still 30 A, so a 30 A continuous load is safe across the full operating range. The TM210 release uses a fixed thermal element and magnetic trip; no interchangeable trip units, so the breaker is matched to the load at the factory. Rated insulation voltage is 800 V, and the maximum operating voltage is 690 V AC, covering 400/480/600 V class systems. Power loss is 10.6 W at rated current — modest for a 32 A frame, but worth checking if the panel has tight thermal budgeting. Interrupting capacity varies with system voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 500 V and 690 V. The breaker carries no trip indicator and no undervoltage release, so remote tripping or status feedback requires an external shunt or UVR accessory. ## Panel integration The 130 mm height and 76.2 mm width leave room for adjacent breakers and busbar connections in a multi-pole lineup.","metaTitle":"Siemens 3VA1032-2ED36-0AA0 SENTRON MCCB, 32 A, 3-Pole, 52.5","metaDescription":"Siemens 3VA1032-2ED36-0AA0 SENTRON MCCB, 32 A, 3-pole, TM210 release, 52.5 kA at 240 V, 32 kA at 415 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1032-2ED36-0AA0","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 100 breaking capacity class B Icu=16kA @ 415V 3-pole, line protection TM210, FTFM, In=32A overload protection Ir=32A fixed short-circuit protection Ii=10 x In clamp connection","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"32 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1,5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1cbcd357e65f4f3d0561aaa4ce8d88d9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=372684&mlfb=3VA1032-2ED36-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA1032-2ED36-0AA0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability."},{"question":"Will 3VA1032-2ED36-0AA0 drop into a panel specified around 3VA1020-3ED36-0AA0?","answer":"Yes, the 70 mm depth, 76.2 mm width, and 130 mm height are identical across the 3VA10xx frame — the same mounting footprint and busbar pitch."},{"question":"What compliance documentation does this breaker carry?","answer":"As a SENTRON MCCB, it carries IEC 60947-2 certification and is UL/CSA listed for the North American market. RoHS and REACH declarations are available through Siemens documentation channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-2ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}