{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-2ED36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-2ED36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1, molded case circuit breaker, 3-pole, 32 A (40 °C), 52.5 kA at 240 V, line protection, TM210 release.","salesMarkdown":"The Siemens 3VA1032-2ED36-0AH0 is a SENTRON 3VA1 molded case circuit breaker for line protection, rated 32 A continuous at 40 °C with a TM210 thermal-magnetic release. It interrupts 52.5 kA at 240 V and 32 kA at 415 V, making it a solid pick for a main feeder or large branch in a 400 V panel where you need real fault-clearing headroom without stepping up to a bigger frame. The 32 A continuous rating holds flat from 40 °C up to 50 °C, then only drops to 30 A by 70 °C — so in a warm enclosure you still get nearly the full nameplate. The 52.5 kA at 240 V and 32 kA at 415 V tell you this breaker can sit upstream of a lot of downstream gear without needing a current-limiting fuse ahead of it; those are real SCCR numbers for a 3-pole frame this size. Dimensions are 76.2 mm wide, 130 mm tall, 70 mm deep — it's a standard 3-pole MCCB footprint for a DIN-rail or screw-mount panel. The 70 mm depth leaves room behind the gland plate for wiring without jamming the enclosure door. It's not on any published phase-out or last-time-buy notice. For a BOM freeze, this part is stable — no imminent PCN risk.","metaTitle":"Siemens 3VA1032-2ED36-0AH0 SENTRON MCCB, 32 A, 3-Pole, 52.5","metaDescription":"Siemens 3VA1032-2ED36-0AH0 SENTRON molded case circuit breaker, 3-pole, 32 A at 40 °C, 52.5 kA interrupting at 240 V. Current lifecycle. Quoted to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10322ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=147562&mlfb=3VA1032-2ED36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of this MCCB?","answer":"The 3VA1032-2ED36-0AH0 has a depth of 70 mm (2.76 in), which fits standard panel depths without crowding the gland plate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-2ED36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}