{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-2ED36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-2ED36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3VA1032-2ED36-0HA0, 3-pole, 32 A (40 °C), 52.5 kA at 240 V, TM210 thermal-magnetic release, shunt trip STL, line protection design.","salesMarkdown":"The 52.5 kA interrupting capacity at 240 V gives solid fault-clearing headroom for industrial feeder circuits; at 415 V it still breaks 32 kA. A built-in shunt trip (STL) auxiliary release lets a remote signal or safety circuit open the breaker independently of the overcurrent mechanism — useful for emergency-off or interlock schemes. Three-pole construction with 800 V rated insulation voltage means it suits 400 V three-phase systems with margin. ## Thermal-magnetic curve and release design The TM210 overcurrent release uses a thermal bimetal for overload protection and a magnetic coil for short-circuit response. Rated current holds steady at 32 A from 40 °C up to 50 °C, then gently tapers to 30 A at 70 °C — a mild derating curve that keeps the breaker usable in warm cabinets without oversizing. The magnetic trip threshold (not listed in this data set) typically tracks the TM210 family's fixed multiple of In. No trip indicator is fitted, so fault events won't leave a visual flag on the breaker face. ## Panel integration and auxiliary wiring Mounts into a standard panel cutout for 3VA three-pole frames. The shunt trip (STL) requires a separate control voltage to operate — wire it through a normally-open contact from the safety relay or E-stop circuit. No communication function or measurement capability is built in, so this is a straight protection device, not a smart breaker.","metaTitle":"Siemens 3VA1032-2ED36-0HA0 SENTRON MCCB, 32 A, 3-Pole, Shunt","metaDescription":"Siemens SENTRON 3VA1032-2ED36-0HA0 molded case circuit breaker, 32 A rated at 40 °C, 52.5 kA at 240 V, 3-pole with TM210 release and shunt trip. Current lifecycle. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10322ED360AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=486981&mlfb=3VA1032-2ED36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1032-2ED36-0HA0?","answer":"Pricing and stock are confirmed at quote time. Submit an RFQ through this listing; the sourcing desk will return current availability and a firm price for your quantity."},{"question":"What breaking capacity does this MCCB have at 240 V and 415 V?","answer":"52.5 kA at 240 V and 32 kA at 415 V, per the interrupting ratings on this variant."},{"question":"Will 3VA1032-2ED36-0HA0 drop into a panel specified for 3VA1110-5EF32-0LA0 without rewiring?","answer":"Both are 3-pole SENTRON MCCBs sharing the 3VA frame footprint, so the physical cutout and bus-bar spacing are the same. However, the 3VA1110-5EF32-0LA0 carries different ratings and a different release type — verify the load current and interrupting requirements against your coordination study before substituting."},{"question":"What compliance documentation does this brand provide for 3VA1032-2ED36-0HA0?","answer":"Siemens SENTRON MCCBs typically carry IEC 60947-2 certification and CE marking. RoHS and REACH declarations are available from the manufacturer's documentation portal. Specific UL listing for this variant should be confirmed from the nameplate or Siemens' UL file."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-2ED36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}