{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-2ED36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-2ED36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-2ED36-0JC0, 3-pole molded case circuit breaker, 32 A rated continuous current, 52.5 kA breaking capacity at 240 V, TM210 thermal-magnetic release, shunt trip, IP40 front.","salesMarkdown":"Its interrupting capacity hits 52.5 kA at 240 V and 32 kA at 415 V — enough to clear high-fault scenarios on distribution or feeder circuits without cascading upstream. No trip indicator on the front — you'll rely on the auxiliary contacts or a remote I/O point to confirm state. ## Thermal derating and ambient limits Above that, it derates stepwise: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. The 3-pole footprint matches the standard SENTRON 3VA frame, so if you're swapping from a 3VA1010 or 3VA1020 variant, the mounting holes and busbar spacing are identical — no rewiring of the buswork needed. The shunt trip coil (STL) is wired separately; verify polarity on the auxiliary release per the terminal diagram.","metaTitle":"Siemens 3VA1032-2ED36-0JC0 SENTRON MCCB, 32 A, 52.5 kA at 24","metaDescription":"Siemens SENTRON 3VA1032-2ED36-0JC0 molded case circuit breaker, 32 A rated, 52.5 kA breaking at 240 V. 3-pole, TM210 release, shunt trip. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"32 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=175219&mlfb=3VA1032-2ED36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0JC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1032-2ED36-0JC0?","answer":"Submit an RFQ through this listing. We source this part to order and confirm current pricing and lead time at quote time."},{"question":"What are the key ratings for 3VA1032-2ED36-0JC0?","answer":"Rated continuous current Iu is 32 A, interrupting capacity is 52.5 kA at 240 V and 32 kA at 415 V, insulation voltage Ui is 800 V. It is a 3-pole MCCB with a TM210 thermal-magnetic release and a shunt trip."},{"question":"Will 3VA1032-2ED36-0JC0 drop into a panel specified for 3VA1010-2ED36-0AC0?","answer":"Yes, the 3VA1032 shares the same frame dimensions and mounting pattern as the 3VA1010 series. The 76.2 mm width and 130 mm height are identical, so it fits the same busbar and DIN-rail layout without rewiring."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"The SENTRON 3VA series carries IEC/EN 60947-2 certification. RoHS and REACH declarations are available from Siemens' documentation portal. The reference code per DIN EN 81346-2 is Q."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-2ED36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}