{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-2ED36-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-2ED36-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-2ED36-0KC0, molded case circuit breaker, 3-pole, 32 A, line protection, 52.5 kA at 240 V, 70 mm depth.","salesMarkdown":"The 52.5 kA interrupting rating at 240 V, 32 kA at 415 V, and 7.5 kA at 690 V tell you the fault current it can safely clear at each voltage — critical for selectivity studies and SCCR compliance upstream of a panel. The rated continuous current Iu of 32 A holds across 40 °C to 50 °C, then derates to 28.8 A at 70 °C; that thermal curve governs the actual load you can hang on it in a warm enclosure. Fit: the breaker occupies 130 mm height, 76.2 mm width, 70 mm depth — standard SENTRON 3VA footprint for a 32 A frame. Two HQ auxiliary switches are factory-fitted (the integrated auxiliary trip is order code 3VA9688-0BL33).","metaTitle":"Siemens 3VA1032-2ED36-0KC0 SENTRON MCCB, 32 A, 3-Pole, 52.5","metaDescription":"Siemens SENTRON 3VA1032-2ED36-0KC0 molded case circuit breaker, 32 A rated continuous current, 3-pole, 52.5 kA at 240 V. Quoted to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"32 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=123163&mlfb=3VA1032-2ED36-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-2ED36-0KC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA1032-2ED36-0KC0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quotation; availability and current pricing are confirmed at quote time."},{"question":"What are the key interrupting ratings for the 3VA1032-2ED36-0KC0?","answer":"At 240 V it interrupts 52.5 kA, at 415 V it interrupts 32 kA, at 440 V it interrupts 13.6 kA, and at 690 V it interrupts 7.5 kA."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"The reference code per DIN EN 81346-2 is Q, and the protection class on the front is IP40. The evidence does not list RoHS, REACH, UL, or IEC certificates directly, but SENTRON 3VA breakers are typically UL 489 and IEC 60947-2 listed; confirm the specific certification package with the order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-2ED36-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-2ED36-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}