{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-3ED32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-3ED32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-3ED32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-3ED32-0AE0, 3-pole molded case circuit breaker, 32 A (40 °C), TM210 thermal-magnetic release, 75.6 kA at 240 V, line protection, 70 mm depth × 76.2 mm width.","salesMarkdown":"It carries a TM210 thermal-magnetic release, which gives you an inverse-time thermal trip for overloads and a fixed magnetic trip for short circuits. That's useful if your panel runs warm and you don't want to oversize the breaker. Three poles, so it switches all three phases together. Breaking capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, and it still manages 7.5 kA up at 690 V — enough for most industrial distribution panels without needing a current-limiting upstream device. Width of 76.2 mm is a 3-pole frame; if you're replacing an existing SENTRON 3VA1 or 3VA2 breaker, the footprint matches. It ships with provision for up to four auxiliary switches (HQ design), which is handy if you need status feedback back to a PLC or a remote monitoring system.","metaTitle":"Siemens 3VA1032-3ED32-0AE0 SENTRON MCCB, 32A, 3-Pole, 75.6kA","metaDescription":"Siemens 3VA1032-3ED32-0AE0 SENTRON molded case circuit breaker, 32A rated at 40°C, 3-pole, 75.6kA breaking at 240V. TM210 release, line protection. Active production. Available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10323ED320AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=79900&mlfb=3VA1032-3ED32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1032-3ED32-0AE0 at different voltages?","answer":"At 240 V it breaks 75.6 kA, at 415 V it breaks 52.5 kA, at 440 V it breaks 32 kA, and at 500 V and 690 V it breaks 7.5 kA."},{"question":"What does the TM210 release mean on this MCCB?","answer":"TM210 is a thermal-magnetic release: the thermal element provides inverse-time overload protection (trip curve adjusts with heat), and the magnetic element gives a fixed instantaneous trip for short circuits. It's a standard line-protection release, not adjustable."},{"question":"Where can I buy 3VA1032-3ED32-0AE0 and what is the price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send a request and we'll get you a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-3ED32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-3ED32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}