{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-3ED32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-3ED32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-3ED32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-3ED32-0HC0, 3-pole molded case circuit breaker, 32 A rated at 40 °C, breaking capacity 75.6 kA at 240 V, line protection design, with shunt trip and 2 auxiliary switches HQ.","salesMarkdown":"Breaking capacity varies with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. This means the breaker can handle high fault currents on lower-voltage networks while still providing adequate interruption on 690 V systems. For a 400 V distribution board, the 52.5 kA figure gives solid selectivity headroom against upstream devices. The breaker holds its full 32 A rating from 40 °C up to 50 °C, then derates to 31 A at 55–60 °C, and 30 A at 65–70 °C. Maximum power loss is 10.6 W. In a warm panel, expect to stay at 32 A unless the internal temperature exceeds 50 °C. Width at 76.2 mm is three 25.4 mm pole pitches — a standard 3-pole MCCB footprint. No communication function or undervoltage release on this variant; the trip indicator is also absent.","metaTitle":"Siemens 3VA1032-3ED32-0HC0 SENTRON MCCB, 32A, 75.6kA at 240V","metaDescription":"Siemens 3VA1032-3ED32-0HC0 SENTRON molded case circuit breaker, 32A rated, 3-pole, 75.6kA breaking at 240V. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10323ED320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=398834&mlfb=3VA1032-3ED32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3VA1032-3ED32-0HC0?","answer":"The 3VA1010-3ED36-0AA0 is a lower-current sibling in the same SENTRON 3VA platform. The key difference is the current rating: the 3VA1032-3ED32-0HC0 is rated 32 A, while the 3VA1010-3ED36-0AA0 is rated 10 A. Both share the same 3-pole form factor and similar breaking capacity class, so panel cutout and busbar spacing are identical — no rewiring needed for the footprint, but the thermal trip setting must match the load."},{"question":"Where can I buy 3VA1032-3ED32-0HC0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send the quantity for a firm offer."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a SENTRON series MCCB, it is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are standard with the documentation package. Specific certs (UL, CSA, CE) should be confirmed at order for the target jurisdiction."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-3ED32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-3ED32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}