{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-3ED36-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-3ED36-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-3ED36-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED36-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-3ED36-0CC0, molded case circuit breaker, 3-pole, 32 A rated continuous current, TM210 thermal-magnetic release, 75.6 kA interrupting at 240 V, undervoltage release, 2 auxiliary switches HQ, IP40 front.","salesMarkdown":"The Siemens SENTRON 3VA1032-3ED36-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 32 A at 40 °C through 50 °C with no derating — it holds 32 A flat across that band, then steps down to 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. That thermal curve means a panel at 50 °C ambient still gets full rated current; above that, the breaker self-protects. Interrupting capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — the 415 V figure is the one that matters for most European 400 V distribution panels, where it clears a 52.5 kA fault without cascading upstream. Front IP40 keeps out tools and debris in a clean panel; the latching endurance is rated at 15 000 operations. Dimensions: 76.2 mm wide, 130 mm high, 70 mm deep — a standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration. The 70 mm depth means it clears most shallow enclosures; the 76.2 mm width matches the typical 3-module slot on a DIN rail.","metaTitle":"Siemens 3VA1032-3ED36-0CC0 SENTRON MCCB, 32 A, 3-Pole, 75.6","metaDescription":"Siemens SENTRON 3VA1032-3ED36-0CC0 molded case circuit breaker, 32 A, 3-pole, 75.6 kA at 240 V. TM210 release, undervoltage release, IP40 front. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"32 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=277089&mlfb=3VA1032-3ED36-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED36-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1032-3ED36-0CC0 and what is the lead time?","answer":"This part is sourced and quoted to order through our independent distribution network. Availability and current lead time are confirmed at quote time against an RFQ — no stock count or shipping promise is published here."},{"question":"What are the key interrupting ratings for 3VA1032-3ED36-0CC0?","answer":"75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. The 415 V figure is the critical one for 400 V distribution panels."},{"question":"What is the rated continuous current of this MCCB?","answer":"32 A at 40 °C through 50 °C with no derating. Above 50 °C it steps down: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C."},{"question":"What auxiliary contacts does this breaker include?","answer":"It includes 2 auxiliary switches HQ (high-quantity) and an undervoltage release (UVR) as the auxiliary release. The integrated auxiliary trip order code is 3VA9608-0BB24."},{"question":"What are the physical dimensions of 3VA1032-3ED36-0CC0?","answer":"Width 76.2 mm, height 130 mm, depth 70 mm. Standard 3-pole MCCB footprint for DIN-rail mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-3ED36-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-3ED36-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}