{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-3ED36-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-3ED36-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-3ED36-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED36-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-3ED36-0DA0, 3-pole molded case circuit breaker, 32 A rated continuous current (Iu), TM210 thermal-magnetic release, line protection version.","salesMarkdown":"The 3VA1032-3ED36-0DA0 is a 3-pole SENTRON MCCB rated for 32 A continuous at 40 °C, and it holds that rating flat through 50 °C — only starts derating above 55 °C, where it drops to 30.72 A, then 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. That thermal curve means a panel running at 50 °C ambient still gets full 32 A capacity; no need to oversize for a warm enclosure. The interrupting ratings climb with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. The TM210 thermal-magnetic release handles line protection, no communication module or phase-failure detection on this variant. ## Panel integration Mounts on a DIN rail or panel-mount base — the 70 mm depth, 76.2 mm width, and 130 mm height fit standard SENTRON 3VA footprint. No auxiliary contact version fitted on this order code — if you need status feedback, you'll add a separate auxiliary switch block.","metaTitle":"Siemens 3VA1032-3ED36-0DA0 SENTRON MCCB, 32 A, 3-Pole, TM210","metaDescription":"Siemens 3VA1032-3ED36-0DA0 SENTRON 3-pole MCCB, 32 A rated, TM210 release, 75.6 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"32 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=351493&mlfb=3VA1032-3ED36-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED36-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1032-3ED36-0DA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What are the key interrupting ratings for this MCCB?","answer":"At 240 V it interrupts 75.6 kA; at 415 V, 52.5 kA; at 440 V, 32 kA; and at 690 V, 7.5 kA. The 440 V figure is the one to check for 480 V panel SCCR coordination."},{"question":"Will 3VA1032-3ED36-0DA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"Both are SENTRON 3VA frame MCCBs with the same 70 mm depth, 76.2 mm width, and 130 mm height footprint, so mechanical fit is identical. The key difference is the continuous rating: this one is 32 A versus the 3VA1010's lower rating. Check that the load and upstream protection are sized for 32 A before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-3ED36-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-3ED36-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}