{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-3ED36-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-3ED36-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-3ED36-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED36-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-3ED36-0DH0, molded case circuit breaker, 3-pole, 32 A, interrupting 75.6 kA at 240 V, line protection design with undervoltage release.","salesMarkdown":"Its interrupting capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — figures that govern the available fault current it can safely clear without upstream coordination failure. Maximum power loss is 13.1 W. The 70 mm depth, 76.2 mm width, and 130 mm height fit a compact 3-pole footprint — check gland-plate clearance if retrofitting into a densely packed panel. At 55 °C it derates to 31 A, at 65 °C to 30 A, and at 70 °C to 30 A.","metaTitle":"Siemens SENTRON 3VA1032-3ED36-0DH0 MCCB, 32 A, 3-Pole, 75.6","metaDescription":"Siemens SENTRON 3VA1032-3ED36-0DH0 molded case circuit breaker, 32 A, 3-pole, interrupting 75.6 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"13.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10323ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=234601&mlfb=3VA1032-3ED36-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-3ED36-0DH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1032-3ED36-0DH0?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time. Submit an RFQ for a firm quote."},{"question":"What is 3VA1032-3ED36-0DH0's interrupting capacity at 415 V?","answer":"52.5 kA at 415 V. At 240 V it is 75.6 kA, at 440 V it is 32 kA, and at 500 V / 690 V it is 7.5 kA."},{"question":"What compliance documentation does this brand provide for 3VA1032-3ED36-0DH0?","answer":"The brand is Siemens SENTRON. Standard documentation includes RoHS, REACH, and IEC/UL compliance declarations; specific certificates are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-3ED36-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-3ED36-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}