{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-4ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-4ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-4ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-4ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-4ED36-0AA0, molded case circuit breaker, 3-pole, 32 A, TM210 overcurrent release, line protection, breaking capacity 121 kA at 240 V.","salesMarkdown":"## Siemens SENTRON 3VA1032-4ED36-0AA0 — 32 A MCCB, line protection Its TM210 overcurrent release provides fixed thermal-magnetic protection — thermal for overloads, magnetic for short-circuits — with no undervoltage release or trip indicator fitted on this variant. Breaking capacity reaches 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V, giving ample SCCR headroom for most low-voltage distribution applications. Rated insulation voltage is 800 V, and the breaker maintains full 32 A rating up to 50 °C ambient; derating begins at 55 °C (31 A) and reaches 30 A at 70 °C. ## Panel fit and thermal management The breaker occupies 76.2 mm width, 130 mm height, and 70 mm depth — a standard 3-pole MCCB footprint that drops into most DIN-rail or panel-mount enclosures without re-drilling. Maximum power loss is 10.6 W. No communication function, ground-fault monitoring, or voltage-trigger features are built in — this is a straight line-protection MCCB with no auxiliary electronics.","metaTitle":"3VA1032-4ED36-0AA0 SENTRON MCCB, 32 A, 3-pole, line protecti","metaDescription":"Siemens SENTRON 3VA1032-4ED36-0AA0 molded case circuit breaker, 32 A rated, 3-pole, TM210 release, breaking capacity 121 kA at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"31 A","at 60 °C":"31 A","at 65 °C":"30 A","at 70 °C":"30 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"32 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d78fa564c23047dd96671bad43e30512.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=465059&mlfb=3VA1032-4ED36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-4ED36-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-4ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-4ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}