{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1032-4ED36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1032-4ED36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1032-4ED36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1032-4ED36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1032-4ED36-0JH0, Molded case circuit breaker, 3-pole, TM210 thermal-magnetic release, 32 A rated continuous current, 121 kA breaking capacity at 240 V.","salesMarkdown":"It carries a rated continuous current Iu of 32 A at ambient temperatures up to 50 °C — no derating needed in a typical 40 °C panel — and begins derating above 55 °C, reaching 28.8 A at the 70 °C operating maximum. Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. That's enough to interrupt high-fault conditions on most commercial and industrial secondary distribution without cascading upstream — the 415 V figure covers common 400 V class panels. The auxiliary release is ordered separately as 3VA9688-0BL32. The SENTRON series carries CE, UL, and IEC certifications per Siemens standard practice. RoHS and REACH declarations are available from the manufacturer upon request. Mount it inside a panel with a door or cover; it is not intended for open washdown areas. The 3-pole footprint is standard for a 32 A MCCB, so it fits existing SENTRON or comparable DIN-rail or screw-mount backplates. A voltage trigger and trip indicator are present on the front, allowing quick visual confirmation of a tripped state during fault isolation — no need to break the seal to check.","metaTitle":"3VA1032-4ED36-0JH0 SENTRON MCCB, 32 A, 3-pole, TM210, 121 kA","metaDescription":"Siemens SENTRON 3VA1032-4ED36-0JH0 molded case circuit breaker, 32 A, 3-pole, TM210 release, 121 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"32 A","at 45 °C":"32 A","at 50 °C":"32 A","at 55 °C":"30.72 A","at 60 °C":"30.08 A","at 65 °C":"29.44 A","at 70 °C":"28.8 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"32 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"32 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"32 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=62024&mlfb=3VA1032-4ED36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1032-4ED36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA1032-4ED36-0JH0's listed depth and width?","answer":"Depth is 70 mm; width is 76.2 mm."},{"question":"Will 3VA1032-4ED36-0JH0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"Both are 3-pole SENTRON MCCBs in the same physical frame class, so the mounting footprint and bus-bar spacing are identical. No rewiring needed for the power connections. Verify that the auxiliary contact arrangement matches your control wiring — the 3VA1032-4ED36-0JH0 carries 2 aux switches plus a trip alarm, which may differ from the 3VA1110-5EE32-0JA0 configuration."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1032-4ED36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1032-4ED36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}