{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1050-3ED36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1050-3ED36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1050-3ED36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1050-3ED36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1050-3ED36-0JC0, molded case circuit breaker, 3-pole, 50 A (40 °C), 75.6 kA at 240 V, line protection, with shunt trip and 2 auxiliary switches.","salesMarkdown":"It carries 50 A continuously at 40 °C and delivers a 75.6 kA interrupting capacity at 240 VAC — enough to handle high-fault utility feeds or transformer secondaries in a distribution panel. The 50 A rating holds steady from 40 °C through 50 °C, then derates to 49 A at 55 °C and 45 A at 70 °C — useful to know if the breaker sits near other heat sources in a crowded enclosure. The 75.6 kA at 240 V is the headline fault-clearing number; at 415 V it still breaks 52.5 kA, and at 690 V it holds 7.5 kA. The 3-pole construction fits standard three-phase feeders — motor branch circuits, lighting panels, or sub-feed distribution. ## Built-in accessories and panel integration The shunt trip allows remote tripping from a PLC or emergency-stop circuit; the auxiliary switches provide status feedback — open/closed indication to a control system or indicator lamp. No field-add-on kit needed for these functions. Dimensions are 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits SENTRON panelboards and most DIN-rail adapters.","metaTitle":"Siemens SENTRON 3VA1050-3ED36-0JC0 MCCB, 50 A, 75.6 kA at 24","metaDescription":"Siemens SENTRON 3VA1050-3ED36-0JC0 molded case circuit breaker, 3-pole, 50 A rated at 40 °C, 75.6 kA breaking capacity at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"49 A","at 60 °C":"48 A","at 65 °C":"46 A","at 70 °C":"45 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"14.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10503ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=197647&mlfb=3VA1050-3ED36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1050-3ED36-0JC0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1050-3ED36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1050-3ED36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}