{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1050-4ED36-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1050-4ED36-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1050-4ED36-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1050-4ED36-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1050-4ED36-0CA0, molded case circuit breaker, 3-pole, 50 A rated continuous current, breaking capacity 121 kA at 240 V, TM210 overcurrent release, with undervoltage release.","salesMarkdown":"The Siemens 3VA1050-4ED36-0CA0 is a 3-pole SENTRON molded case circuit breaker rated for 50 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. Breaking capacity reaches 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — per the datasheet, these are the values that govern selectivity coordination downstream. There is no auxiliary contact block fitted from the factory, so if you need status feedback to a PLC, plan for the separate 3VA9608-0BB24 auxiliary trip accessory. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — the 76.2 mm width (three 25.4 mm pole pitches) is standard for 3VA frame sizes, so it drops into existing SENTRON busbar systems without adapter plates. ## Current rating across temperature — the real derating curve Above that, it steps down: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. If your panel ambient runs at 60 °C, the usable current is 47 A — not the nameplate 50 A. ## Mechanical endurance and release configuration Rated for 15,000 mechanical latching operations — that is the endurance figure for the mechanism, not the electrical switching life under load. It is a line-protection product, not a motor-protection or ground-fault device.","metaTitle":"Siemens 3VA1050-4ED36-0CA0 SENTRON MCCB, 50A, 121kA at 240V","metaDescription":"Siemens 3VA1050-4ED36-0CA0 SENTRON molded case circuit breaker, 3-pole, 50A rated, breaking capacity 121kA at 240V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"48 A","at 60 °C":"47 A","at 65 °C":"46 A","at 70 °C":"45 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"50 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"50 A","Adjustable response value current / li max.":"500 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"50 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=392176&mlfb=3VA1050-4ED36-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1050-4ED36-0CA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1050-4ED36-0CA0 and how do I get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1050-4ED36-0CA0 at different voltages?","answer":"Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — these are the values for selectivity coordination."},{"question":"Does 3VA1050-4ED36-0CA0 include an undervoltage release?","answer":"Yes, it is fitted with an undervoltage release (UVR) as the auxiliary release. No auxiliary contact block is included from the factory."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1050-4ED36-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1050-4ED36-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}