{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1050-4ED36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1050-4ED36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1050-4ED36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1050-4ED36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1050-4ED36-0JH0, molded case circuit breaker, 3-pole, 50 A rated at 40 °C, 121 kA breaking capacity at 240 V, line protection design.","salesMarkdown":"## Siemens SENTRON 3VA1050-4ED36-0JH0 — 50 A MCCB for Line Protection At 415 V the rating drops to 75.6 kA, at 440 V to 52.5 kA, and at 500 V or 690 V it holds at 11.9 kA. The breaker carries a full 50 A from 40 °C up through 50 °C. At 55 °C it derates to 49 A, at 60 °C to 48 A, at 65 °C to 46 A, and at 70 °C to 45 A. ## Physical Fit and Auxiliary Options The 3VA1050-4ED36-0JH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. A shunt trip release (STL) is also fitted. The trip indicator and voltage trigger are present, but undervoltage release and ground-fault monitoring are not included on this variant.","metaTitle":"Siemens 3VA1050-4ED36-0JH0 SENTRON MCCB, 50A, 121kA at 240V","metaDescription":"Siemens SENTRON 3VA1050-4ED36-0JH0 molded case circuit breaker, 3-pole, 50A rated at 40°C, 121kA breaking at 240V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"49 A","at 60 °C":"48 A","at 65 °C":"46 A","at 70 °C":"45 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"14.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10504ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=530234&mlfb=3VA1050-4ED36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1050-4ED36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA1050-4ED36-0JH0 and how is it quoted for volume purchases?","answer":"It is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1050-4ED36-0JH0 at different voltages?","answer":"121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V."},{"question":"What auxiliary switches and releases come with 3VA1050-4ED36-0JH0?","answer":"It includes 2 auxiliary switches plus 1 trip alarm switch (HQ), and a shunt trip release (STL)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1050-4ED36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1050-4ED36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}