{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1050-4ED42-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1050-4ED42-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1050-4ED42-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1050-4ED42-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1050-4ED42-0DC0, molded case circuit breaker, 4-pole, 50 A rated continuous current, breaking capacity 121 kA at 240 V, TM210 overcurrent release, undervoltage release, IP40 front.","salesMarkdown":"Breaking capacity hits 121 kA at 240 V, dropping to 75.6 kA at 415 V and 52.5 kA at 440 V — numbers that tell you this unit handles high-fault utility feeds or transformer secondaries without cascading upstream. Current rating holds flat at 50 A from 40 °C through 50 °C ambient, then derates to 48 A at 55 °C and 45 A at 70 °C. That means in a hot enclosure — say a non-ventilated panel near a furnace line — you don't lose headroom until past 50 °C, which is better than many MCCBs that start derating at 40 °C. Dimensions are 101.6 mm wide by 130 mm tall by 70 mm deep — a 4-pole MCCB that fits the standard SENTRON mounting footprint. Front IP40 protection means it's fine inside a closed panel but not for washdown environments. No trip indicator on the front face, so fault diagnostics rely on the auxiliary switch feedback or a visual check of the handle position.","metaTitle":"Siemens 3VA1050-4ED42-0DC0 SENTRON MCCB, 50 A, 4-Pole, 121 k","metaDescription":"Siemens SENTRON 3VA1050-4ED42-0DC0 molded case circuit breaker, 50 A rated continuous current, 4-pole, breaking capacity 121 kA at 240 V. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"50 A","at 45 °C":"50 A","at 50 °C":"50 A","at 55 °C":"48 A","at 60 °C":"47 A","at 65 °C":"46 A","at 70 °C":"45 A","Trip indicator":"No","Number of poles":"4","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"50 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"Without","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"600 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"50 A","Adjustable response value current / li max.":"500 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"50 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=491046&mlfb=3VA1050-4ED42-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1050-4ED42-0DC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1050-4ED42-0DC0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA1050-4ED42-0DC0 at different voltages?","answer":"Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. At 690 V the rating drops sharply — verify the available fault current at your system voltage before specifying."},{"question":"Does 3VA1050-4ED42-0DC0 have an undervoltage release?","answer":"Yes, it comes with an undervoltage release (UVR) as standard. The auxiliary release design is specified as undervoltage release (UVR), and it also includes two auxiliary switches (HQ type)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1050-4ED42-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1050-4ED42-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}