{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1063-2ED32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1063-2ED32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1063-2ED32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1063-2ED32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1063-2ED32-0AH0, 3-pole molded case circuit breaker, 63 A rated continuous current, 52.5 kA breaking capacity at 240 V, TM210 thermal-magnetic release, IP40 front.","salesMarkdown":"The Siemens 3VA1063-2ED32-0AH0 is a 3-pole SENTRON molded case circuit breaker rated for 63 A continuous current at 40 °C, holding that rating through 50 °C before a gentle derate to 56.7 A at 70 °C. Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — sufficient for most industrial distribution panels where fault current stays under those thresholds. The TM210 thermal-magnetic release is fixed, not adjustable, so the trip curve is set at the factory; no field tweaking of the magnetic pickup. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a 3-pole MCCB footprint that fits standard SENTRON mounting plates and busbar systems. Front face carries IP40 protection, meaning tools and fingers are kept out, but the breaker is intended for enclosed panel mounting rather than open washdown areas.","metaTitle":"Siemens 3VA1063-2ED32-0AH0 SENTRON MCCB, 63 A, 52.5 kA","metaDescription":"Siemens 3VA1063-2ED32-0AH0 SENTRON molded case circuit breaker, 3-pole, 63 A rated, 52.5 kA breaking at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=62008&mlfb=3VA1063-2ED32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1063-2ED32-0AH0/alternatives.json"},"ai":{"faq":[{"question":"What type of overcurrent release does this breaker use?","answer":"A TM210 thermal-magnetic release — fixed trip settings, not field-adjustable."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1063-2ED32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1063-2ED32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}