{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1063-2ED36-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1063-2ED36-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1063-2ED36-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1063-2ED36-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1063-2ED36-0HC0, 3-pole molded case circuit breaker, 63 A rated continuous current, 52.5 kA breaking capacity at 240 V, line protection version with TM210 thermal-magnetic release.","salesMarkdown":"## Siemens SENTRON 3VA1063-2ED36-0HC0 — 63 A MCCB with shunt trip The Siemens SENTRON 3VA1063-2ED36-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 63 A up to 50 °C and derating to 56.7 A at 70 °C. Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, and 7.5 kA at 690 V — figures that govern the available fault current the breaker can safely interrupt at the service voltage. The 63 A frame holds its full rating through 50 °C ambient — above that the thermal derating curve drops to 60.48 A at 55 °C and 56.7 A at 70 °C. The 52.5 kA at 240 V and 32 kA at 415 V are the SCCR the breaker contributes to the panel label; a downstream fault exceeding those values risks the breaker failing to clear. The shunt trip (STL) is wired separately from the main circuit — it needs a control voltage to fire, and the breaker has no undervoltage release or ground-fault module on this variant. The 3VA1063-2ED36-0HC0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole frame that fits standard SENTRON mounting plates and busbar systems. The integrated shunt trip order code is 3VA9688-0BL30, which ships pre-installed.","metaTitle":"Siemens 3VA1063-2ED36-0HC0 SENTRON MCCB, 63 A, 52.5 kA at 24","metaDescription":"Siemens SENTRON 3VA1063-2ED36-0HC0 molded case circuit breaker, 63 A rated, 52.5 kA breaking capacity at 240 V. Line protection, 3-pole, shunt trip. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=473043&mlfb=3VA1063-2ED36-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1063-2ED36-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1063-2ED36-0HC0 at 415 V?","answer":"The breaking capacity is 32 kA at 415 V, with higher ratings of 52.5 kA at 240 V and lower ratings of 13.6 kA at 440 V and 7.5 kA at 690 V."},{"question":"Does 3VA1063-2ED36-0HC0 include a shunt trip?","answer":"Yes, it includes a factory-fitted shunt trip (STL) with the integrated auxiliary trip order code 3VA9688-0BL30. It does not include an undervoltage release or ground-fault monitoring."},{"question":"Where can I buy 3VA1063-2ED36-0HC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1063-2ED36-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1063-2ED36-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}