{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1063-2ED36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1063-2ED36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1063-2ED36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1063-2ED36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1063-2ED36-0JA0, molded case circuit breaker, 3-pole, 63 A, TM210 release, 52.5 kA at 240 V, shunt trip.","salesMarkdown":"The Siemens SENTRON 3VA1063-2ED36-0JA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with the TM210 thermal-magnetic release handling overload and short-circuit protection. That 63 A holds steady up to 50 °C; above that it derates to 60.48 A at 55 °C and 56.7 A at 70 °C — so if your panel ambient runs hot, you lose about 10% headroom at the top end. Breaking capacity runs 52.5 kA at 240 V, drops to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. That 52.5 kA at 240 V gives you serious fault-clearing headroom on a 480Y/277 V secondary or a 240 V delta service — the SCCR on the line side can ride higher than most panelboards are rated for. It's a straight line-protection breaker — no bells, no bus taps. The breaker measures 70 mm deep by 76.2 mm wide by 130 mm tall — a standard 3-pole MCCB footprint that drops into most SENTRON panelboards and DIN-rail adapters without re-drilling the gland plate. The 76.2 mm width matches the typical 3-pole cutout; verify your busbar spacing if you're retrofitting into a non-Siemens panel. The 3VA1110-5EE32-0JA0 is a higher-rated sibling — 100 A frame, electronic release, likely a different trip curve and higher interrupting capacity. The 3VA1063-2ED36-0JA0 is the 63 A thermal-magnetic version with a shunt trip. If your BOM calls for 63 A and a TM release, this is the one; the 1110 frame won't drop in without re-terminating the load cables and checking the busbar ampacity.","metaTitle":"Siemens 3VA1063-2ED36-0JA0 SENTRON MCCB, 63 A, 3-Pole, TM210","metaDescription":"Siemens SENTRON 3VA1063-2ED36-0JA0 molded case circuit breaker, 63 A continuous, 3-pole, TM210 thermal-magnetic release, 52.5 kA at 240 V. Active production. Available to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=511321&mlfb=3VA1063-2ED36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1063-2ED36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA1063-2ED36-0JA0 include a shunt trip?","answer":"Yes, it includes a shunt trip (STL) auxiliary release; the integrated trip unit order code is 3VA9688-0BL32."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1063-2ED36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1063-2ED36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}