{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1063-3ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1063-3ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1063-3ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1063-3ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1063-3ED32-0AA0, 3-pole molded case circuit breaker, 63 A at 40 °C, 75.6 kA interrupting at 240 V, TM210 release.","salesMarkdown":"The Siemens SENTRON 3VA1063-3ED32-0AA0 is a 3-pole molded case circuit breaker rated 63 A at 40 °C, with a TM210 thermal-magnetic release for line protection. Interrupting capacity hits 75.6 kA at 240 V, stepping down to 52.5 kA at 415 V and 32 kA at 440 V — enough headroom for most distribution panels feeding motor control centers or lighting subboards. The TM210 release means the thermal pickup is fixed at 1.0× the frame rating, magnetic trip at 10× In — a standard curve for general distribution, not for motor-starting duty. Rated 63 A from 40 °C through 50 °C, then derates: 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, 58 A at 70 °C. If the panel ambient runs at 65 °C, the breaker is good for 60 A continuous — plan your load schedule accordingly. Power loss maxes at 17.3 W, which matters for enclosure heat rise calculations in a packed cabinet. Width at 76.2 mm (3 in) is standard for a 3-pole MCCB in this frame size — drops into the same cutout as other SENTRON 3VA breakers. No trip indicator, no voltage trigger — the front face stays clean.","metaTitle":"Siemens 3VA1063-3ED32-0AA0 SENTRON MCCB, 63 A, 75.6 kA","metaDescription":"Siemens SENTRON 3VA1063-3ED32-0AA0 molded case circuit breaker, 3-pole, 63 A at 40 °C, 75.6 kA at 240 V. TM210 release. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1063-3ED32-0AA0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 100 breaking capacity class N Icu=25kA @ 415V 3-pole, line protection TM210, FTFM, In=63A overload protection Ir=63A fixed short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/199b2fe0692baf6ec3c2d2b3b9c78bd4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=469063&mlfb=3VA1063-3ED32-0AA0"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1063-3ED32-0AA0 at 240 V?","answer":"75.6 kA at 240 V, stepping to 52.5 kA at 415 V and 32 kA at 440 V."},{"question":"Where can I buy 3VA1063-3ED32-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What does the TM210 release mean on this MCCB?","answer":"TM210 is a thermal-magnetic release with fixed thermal pickup at 1.0× In and magnetic trip at 10× In — a standard curve for line protection in distribution panels, not for motor starting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1063-3ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1063-3ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}