{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1063-3ED36-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1063-3ED36-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1063-3ED36-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1063-3ED36-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1063-3ED36-0KH0, molded case circuit breaker, 3-pole, 63 A rated at 40 °C, breaking capacity 75.6 kA at 240 V, line protection design.","salesMarkdown":"## 63 A MCCB with voltage-graded interrupting ratings Per the datasheet, the current holds flat at 63 A through 50 °C, then derates to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C — so the full rating is available across most panel interior temperatures without a derate factor. Breaking capacity varies by system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. At 690 V the 7.5 kA rating limits application to lower-fault installations. The 3-pole footprint fits standard MCCB panel cutouts and DIN-rail adapter plates. The 17.3 W power loss at full load should be factored into enclosure thermal calculations, especially in sealed cabinets.","metaTitle":"Siemens 3VA1063-3ED36-0KH0 SENTRON MCCB, 63A, 75.6kA at 240V","metaDescription":"Siemens SENTRON 3VA1063-3ED36-0KH0 molded case circuit breaker, 3-pole, 63A rated at 40°C, breaking capacity 75.6kA at 240V. Active lifecycle. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"17.3 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10633ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=276506&mlfb=3VA1063-3ED36-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1063-3ED36-0KH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1063-3ED36-0KH0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit a request for a firm quote on your volume."},{"question":"What is the breaking capacity of 3VA1063-3ED36-0KH0 at different voltages?","answer":"75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V."},{"question":"Does 3VA1063-3ED36-0KH0 include auxiliary switches or a shunt trip?","answer":"Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ), and a shunt trip (STL) release. No undervoltage release or ground-fault monitoring on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1063-3ED36-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1063-3ED36-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}