{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1063-4ED32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1063-4ED32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1063-4ED32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1063-4ED32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1063-4ED32-0DA0, molded case circuit breaker, 3-pole, 63 A, TM210 thermal-magnetic release, 121 kA at 240 V, undervoltage release, IP40 front.","salesMarkdown":"That TM210 designation means the thermal element is fixed at 63 A (the frame rating) and the magnetic short-circuit pickup is adjustable — typically 5–10× In, so about 315–630 A instantaneous trip. The 121 kA interrupting rating at 240 V AC tells you this breaker can clear a bolted fault at that level without venting or welding contacts; at 415 V it still holds 75.6 kA, and at 690 V it drops to 11.9 kA. For a 480 V panel, the relevant figure is the 415 V column — 75.6 kA SCCR headroom is enough for most industrial service entrances. At 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A. Width is 76.2 mm (roughly 3 inches), depth is 70 mm, height is 130 mm. ## What the TM210 release means in practice The TM210 is a thermal-magnetic release with a fixed thermal element and adjustable magnetic pickup. The '210' code indicates the frame size and trip characteristics — it's the standard line-protection version, not a motor-protection or electronic release. That means it's sized for cable and busbar protection, not for motor overload curves. If you need adjustable thermal settings or ground-fault protection, you'd step up to an electronic release (e.g., ETU series) in a different 3VA variant.","metaTitle":"Siemens 3VA1063-4ED32-0DA0 SENTRON MCCB, 63 A, 3-Pole, TM210","metaDescription":"Siemens SENTRON 3VA1063-4ED32-0DA0 molded case circuit breaker. 63 A continuous, 121 kA at 240 V, 3-pole, TM210 release, undervoltage release. Active production, available to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"60.48 A","at 60 °C":"59.22 A","at 65 °C":"57.96 A","at 70 °C":"56.7 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"63 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"63 A","Adjustable response value current / li max.":"630 A","Adjustable response value current / li min.":"630 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=380180&mlfb=3VA1063-4ED32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1063-4ED32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA1063-4ED32-0DA0 at 240 V?","answer":"121 kA at 240 V AC. At 415 V it's 75.6 kA, at 440 V it's 52.5 kA, and at 690 V it's 11.9 kA."},{"question":"Will 3VA1063-4ED32-0DA0 drop into a panel specified for 3VA1112-5EF32-0CA0?","answer":"Physically yes — both are 3VA1 frame size with the same 76.2 mm width and 70 mm depth. The difference is rating: the 3VA1112-5EF32-0CA0 is a higher-current variant with a different trip unit. Check your load current and SCCR requirements before swapping."},{"question":"Where can I buy 3VA1063-4ED32-0DA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"The SENTRON 3VA series carries UL, CSA, and IEC certifications. RoHS and REACH declarations are available from Siemens' documentation portal. The reference code per DIN EN 81346-2 is Q."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1063-4ED32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1063-4ED32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}