{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1063-4ED36-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1063-4ED36-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1063-4ED36-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1063-4ED36-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1063-4ED36-0BC0, molded case circuit breaker, 3-pole, 63 A rated current at 40 °C, interrupting capacity 121 kA at 240 V, line protection design, undervoltage release.","salesMarkdown":"## Siemens SENTRON 3VA1063-4ED36-0BC0 — 63 A MCCB with 121 kA interrupting capacity The Siemens SENTRON 3VA1063-4ED36-0BC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 63 A at 40 °C and an interrupting capacity of 121 kA at 240 V — that figure drops to 75.6 kA at 415 V and 52.5 kA at 440 V, so verify the available fault current at your service voltage before committing the BOM line. Thermal derating is minimal up to 50 °C (still 63 A), then drops to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C — so for a panel running at 60 °C ambient you lose only 2 A of headroom. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — fits standard panel-mount cutouts for 3-pole MCCBs in the 63 A frame class. The auxiliary switch design accommodates two HQ auxiliary switches, and the breaker ships with the basic switch 3VA10634ED360AA0 — verify the auxiliary contact configuration matches your control circuit wiring before panel integration.","metaTitle":"Siemens 3VA1063-4ED36-0BC0 SENTRON MCCB, 63 A, 121 kA at 240","metaDescription":"Siemens SENTRON 3VA1063-4ED36-0BC0 molded case circuit breaker, 3-pole, 63 A rated current, interrupting capacity 121 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"63 A","at 45 °C":"63 A","at 50 °C":"63 A","at 55 °C":"62 A","at 60 °C":"61 A","at 65 °C":"60 A","at 70 °C":"58 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.8 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10634ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=225210&mlfb=3VA1063-4ED36-0BC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1063-4ED36-0BC0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA1063-4ED36-0BC0 include an undervoltage release?","answer":"Yes, the breaker is designed with an undervoltage release (UVR) as part of the auxiliary release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1063-4ED36-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1063-4ED36-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}