{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1080-2ED32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1080-2ED32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1080-2ED32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1080-2ED32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1080-2ED32-0HC0, molded case circuit breaker, line protection, 3-pole, 80 A, TM210 thermal-magnetic release, 52.5 kA at 240 V, shunt trip STL, 2 HQ auxiliary switches.","salesMarkdown":"The TM210 thermal-magnetic release handles overloads and short circuits without external power — the thermal element tracks the load curve, the magnetic element trips instantaneously on high fault current. Breaking capacity hits 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V, so it clears faults up to those levels without upstream cascading. An integrated shunt trip (STL) release (order code 3VA9688-0BL30) and two HQ auxiliary switches are built in, so you can remote-trip the breaker and get status feedback without adding external modules. Footprint is 76.2 mm wide by 130 mm tall by 70 mm deep — standard DIN-rail mount, fits a 3-pole MCCB slot in most SENTRON distribution panels. The 70 mm depth leaves room behind the door for wiring and the shunt trip wiring. Current rating holds at 80 A up to 50 °C, then derates to 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C — plan your enclosure ventilation if the panel runs hot.","metaTitle":"Siemens 3VA1080-2ED32-0HC0 MCCB, 80 A, 3-Pole, TM210, Shunt","metaDescription":"Siemens SENTRON 3VA1080-2ED32-0HC0 molded case circuit breaker, 80 A rated, 3-pole, TM210 thermal-magnetic release, 52.5 kA at 240 V. Current lifecycle stage, sourced to order. Req","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"76.8 A","at 60 °C":"75.2 A","at 65 °C":"73.6 A","at 70 °C":"72 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"80 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"80 A","Adjustable response value current / li max.":"800 A","Adjustable response value current / li min.":"800 A","Adjustable response value current / lr min.":"80 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=234322&mlfb=3VA1080-2ED32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1080-2ED32-0HC0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1080-2ED32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1080-2ED32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}