{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1080-2ED36-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1080-2ED36-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1080-2ED36-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1080-2ED36-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1080-2ED36-0CH0, molded case circuit breaker, 3-pole, 80 A rated continuous current, TM210 thermal-magnetic release, line protection version, IP40 front.","salesMarkdown":"The Siemens SENTRON 3VA1080-2ED36-0CH0 is a 3-pole molded case circuit breaker rated for 80 A continuous current at 40 °C, with a TM210 thermal-magnetic release for line protection. It breaks 52.5 kA at 240 V and 32 kA at 415 V, so it handles high-fault utility feeds or transformer secondaries without cascading upstream. ## Thermal derating and trip hardware The 80 A rating holds flat through 50 °C, then derates to 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C. The TM210 release is thermal-magnetic — fixed thermal curve, magnetic pickup adjustable via the front dial. No voltage trigger, no phase failure detection, no ground fault monitoring; this is a straight line-protection breaker.","metaTitle":"Siemens 3VA1080-2ED36-0CH0 SENTRON MCCB, 80 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA1080-2ED36-0CH0 molded case circuit breaker, 80 A rated at 40 °C, 3-pole, TM210 release, 52.5 kA at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"80 A","at 45 °C":"80 A","at 50 °C":"80 A","at 55 °C":"76.8 A","at 60 °C":"75.2 A","at 65 °C":"73.6 A","at 70 °C":"72 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"80 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"80 A","Adjustable response value current / li max.":"800 A","Adjustable response value current / li min.":"800 A","Adjustable response value current / lr min.":"80 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=529148&mlfb=3VA1080-2ED36-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1080-2ED36-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1080-2ED36-0CH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"Will 3VA1080-2ED36-0CH0 drop into a panel specified around 3VA1010-2ED36-0AC0 without rewiring?","answer":"The 3VA1080-2ED36-0CH0 shares the same 3-pole SENTRON 3VA platform and mounting footprint as the 3VA1010-2ED36-0AC0, so it fits the same panel cutout and bus connections. The key difference is the 80 A continuous rating versus the 3VA1010's lower rating — verify the load current before swapping."},{"question":"What compliance documentation does this brand provide?","answer":"As a current-production Siemens SENTRON MCCB, the 3VA1080-2ED36-0CH0 carries the standard IEC/UL certifications for the series. Documentation includes the device manual (referenced for DC applications), and the part complies with applicable RoHS and REACH requirements per Siemens' standard declarations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1080-2ED36-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1080-2ED36-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}