{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1080-2ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1080-2ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1080-2ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1080-2ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1080-2ED42-0AA0, molded case circuit breaker, 4-pole, 80 A, TM210 thermal-magnetic release, line protection version.","salesMarkdown":"## 80 A, 4-pole MCCB with TM210 release — line protection for distribution panels The Siemens 3VA1080-2ED42-0AA0 is a 4-pole molded case circuit breaker from the SENTRON 3VA series, rated for 80 A continuous at 40 °C and configured for line protection. It carries a TM210 thermal-magnetic release — the fixed thermal element and fixed magnetic trip are factory-set, so no field adjustment of the trip curve is needed. This is the version you spec when the BOM calls for a non-communicating, no-ground-fault, no-N-conductor-protection MCCB that simply clears overloads and short circuits in a distribution panel. This MCCB delivers 52.5 kA at 240 V AC, 32 kA at 415 V AC, 13.6 kA at 440 V AC, and 7.5 kA at both 500 V and 690 V AC. ## Thermal derating — don't size on the 40 °C number alone Above that, it starts to taper: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. The thermal element in the TM210 release responds to ambient heat, so a hot panel reduces headroom. The breaker occupies 101.6 mm (4 in) of width on the DIN rail or mounting plate, with a depth of 70 mm (2.76 in) and height of 130 mm (5.12 in). That width is the critical dimension for multi-breaker layouts — a 4-pole at 101.6 mm means it takes the same space as two standard 2-pole 3VA frames side by side. Max power dissipation is 19.2 W — negligible for thermal planning in a ventilated panel, but worth noting if the breaker is in a sealed, densely packed cabinet. Maximum rated operational voltage with DC is 600 V.","metaTitle":"Siemens 3VA1080-2ED42-0AA0 SENTRON MCCB, 80A, 4-Pole, TM210","metaDescription":"Siemens 3VA1080-2ED42-0AA0 SENTRON molded case circuit breaker, 80 A continuous, 4-pole, TM210 thermal-magnetic release. 52.5 kA at 240 V, 32 kA at 415 V. Current lifecycle stage.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"4","Width":"101.6 mm","Height":"130 mm","Product Status":"Active","Insulation Voltage Ui":"800 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/df894a62387b871c860971ddaad070c1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=35891&mlfb=3VA1080-2ED42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1080-2ED42-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1080-2ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1080-2ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}