{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1080-4ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1080-4ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1080-4ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1080-4ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 100 circuit breaker, 3-pole, breaking capacity class S, Icu=36kA @ 415V, line protection TM210, FTFM, In=80A, Ir=80A fixed, Ii=10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1080-4ED32-0AA0-ZD00 is a 3-pole IEC frame 100 molded case circuit breaker rated 80 A continuous, with a fixed thermal-magnetic trip (TM210, FTFM) and a short-circuit breaking capacity of 36 kA at 415 V (class S). The Ir is fixed at 80 A and the instantaneous magnetic pickup Ii is set at 10 x In (800 A). The fixed Ir at 80 A means the overload protection is not field-adjustable; the breaker is ordered for that exact load current. The fixed Ii at 10 x In (800 A) gives a magnetic trip threshold suited for motor or transformer inrush without nuisance tripping on start-up.","metaTitle":"Siemens 3VA1080-4ED32-0AA0-ZD00 Circuit Breaker, 80A, 36kA @","metaDescription":"Siemens 3VA1080-4ED32-0AA0-ZD00 IEC frame 100 circuit breaker, 3-pole, 80A, 36kA breaking capacity @ 415V. Current lifecycle stage. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c15995e973cd1ad67f19626d7c2e039d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667499&mlfb=3VA1080-4ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1080-4ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1080-4ED32-0AA0-ZD00 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm availability and current pricing."},{"question":"What are the key ratings of this circuit breaker?","answer":"It is a 3-pole IEC frame 100 breaker rated 80 A continuous, with a fixed thermal-magnetic trip (TM210, FTFM), a short-circuit breaking capacity of 36 kA at 415 V (class S), fixed Ir at 80 A, and fixed Ii at 10 x In (800 A)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1080-4ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1080-4ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}