{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-2ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-2ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-2ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1096-2ED32-0AA0, 3-pole molded case circuit breaker, 16 A, TM210 thermal-magnetic release, breaking capacity 52.5 kA at 240 V AC, IP40 front.","salesMarkdown":"## SENTRON 3VA1096-2ED32-0AA0 — 16 A MCCB with TM210 release The Siemens 3VA1096-2ED32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated 16 A continuous at 40 °C, with a TM210 thermal-magnetic release. The TM210 designation means the thermal element is fixed at 16 A (the Iu rating) and the magnetic short-circuit pickup is adjustable from 160 A to 320 A (10–20× In), giving you flexibility to coordinate with downstream branch devices without swapping trip units. Breaking capacity is 52.5 kA at 240 V AC, dropping to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 500 V and 690 V. At 240 V this covers most North American panelboard fault-current requirements; at 415 V it handles European industrial distribution. Thermal derating is minimal through 55 °C — still 16 A — then drops to 15 A at 60 °C through 70 °C. Rated insulation voltage Ui is 800 V, so the breaker is suitable for 480/277 V and 600/347 V systems with margin. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration.","metaTitle":"Siemens 3VA1096-2ED32-0AA0 SENTRON MCCB, 16 A, 52.5 kA at 24","metaDescription":"Siemens 3VA1096-2ED32-0AA0 SENTRON 3-pole MCCB, 16 A rated, TM210 release, breaking capacity 52.5 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1096-2ED32-0AA0","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 100 breaking capacity class B Icu=16kA @ 415V 3-pole, line protection TM210, FTFM, In=16A overload protection Ir=16A fixed short-circuit protection Ii=20 x In nut keeper kit","Number Of Poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"16 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a85ee5ccff733a08dd555b9869f1ac29.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=198113&mlfb=3VA1096-2ED32-0AA0"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1096-2ED32-0AA0 at 415 V?","answer":"32 kA at 415 V AC, which covers most European industrial distribution fault levels."},{"question":"Where can I buy 3VA1096-2ED32-0AA0 and how is it quoted?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."},{"question":"What does the TM210 release mean on this MCCB?","answer":"TM210 means a thermal-magnetic release with a fixed 16 A thermal element and an adjustable magnetic short-circuit pickup from 160 A to 320 A (10–20× In)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-2ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-2ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}