{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-2ED32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-2ED32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-2ED32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1096-2ED32-0DA0, 3-pole molded case circuit breaker, 16 A rated continuous current, TM210 thermal-magnetic trip, breaking capacity 52.5 kA at 240 V.","salesMarkdown":"It's a 3-pole line-protection breaker, meaning it's sized for feeder or branch-circuit duty in a distribution panel, not motor-starting applications. At 415 V it still holds 32 kA, and at 690 V it's rated 7.5 kA — that's the voltage-dependent drop you expect from a compact-frame MCCB. At 55 °C it derates to 15.36 A, at 70 °C to 14.4 A. If your enclosure sits near a heat source or in a non-climate-controlled room, check the actual ambient against that curve. The TM210 is a thermal-magnetic trip — fixed thermal and magnetic settings, no electronic adjustability. That's fine for a straightforward feeder or branch circuit where coordination is set by the breaker size, not a tunable curve. The 3VA1096-2ED32-0DA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. That 76.2 mm width is a 3-pole footprint — it occupies three 25.4 mm modules on a DIN rail or panel-mount base. Standard SENTRON 3VA mounting pattern; it drops into the same cutout as other 3VA frame sizes of the same pole count.","metaTitle":"Siemens 3VA1096-2ED32-0DA0 SENTRON MCCB, 16 A, 52.5 kA at 24","metaDescription":"Siemens 3VA1096-2ED32-0DA0 SENTRON 3-pole molded case circuit breaker, 16 A rated, TM210 trip, 52.5 kA at 240 V. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"15.36 A","at 60 °C":"15.04 A","at 65 °C":"14.72 A","at 70 °C":"14.4 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"16 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"16 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"16 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=308710&mlfb=3VA1096-2ED32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA1096-2ED32-0DA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"At 240 V it's rated 52.5 kA, at 415 V it's 32 kA, at 440 V it's 13.6 kA, and at 690 V it's 7.5 kA."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it ships with an integrated undervoltage release (UVR), order code 3VA9608-0BB25. No auxiliary contacts or shunt trip are included on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-2ED32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-2ED32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}