{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-2ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-2ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-2ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA molded case circuit breaker, 3VA1096-2ED36-0AA0, 3-pole, 16 A rated at 40 °C, TM210 thermal-magnetic release, breaking capacities 52.5 kA at 240 V AC, 32 kA at 415 V AC.","salesMarkdown":"The Siemens 3VA1096-2ED36-0AA0 is a SENTRON molded case circuit breaker (MCCB) for line protection, 3-pole, rated 16 A continuous at 40 °C ambient — and it holds that 16 A rating all the way up to 55 °C, then derates to 15 A at 60 °C through 70 °C. That flat thermal curve means you don't lose headroom in a warm panel unless the ambient hits 60 °C. Breaking capacity steps with system voltage: 52.5 kA at 240 V AC, 32 kA at 415 V AC, 13.6 kA at 440 V AC, and 7.5 kA at both 500 V and 690 V AC. At 240 V this breaker clears a 52.5 kA fault — that's well into high-fault industrial service territory. At 690 V the 7.5 kA rating still covers most motor-circuit fault levels. The TM210 overcurrent release is a thermal-magnetic design — fixed thermal trip for overload, magnetic for short-circuit. The storage minimum covers cold warehouse conditions; the operating range suits most indoor industrial environments.","metaTitle":"Siemens 3VA1096-2ED36-0AA0 SENTRON MCCB, 16 A, 52.5 kA at 24","metaDescription":"Siemens SENTRON 3VA1096-2ED36-0AA0 molded case circuit breaker, 16 A rated, 52.5 kA breaking at 240 V, 3-pole, TM210 release. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Switching Cycles) / Typical":"20 000","reference value setting current (Ii) / for I-tripping":"x In","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","type of value list setting current (Ii) / for I-tripping":"Fest","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1,5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a6771bf1b78085bbcdbc86a96faa1efc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=425405&mlfb=3VA1096-2ED36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED36-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-2ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-2ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}