{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-2ED36-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-2ED36-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-2ED36-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED36-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA molded case circuit breaker, 3VA1096-2ED36-0DA0, 16 A, 3-pole, 52.5 kA interrupting at 240 V, TM210 thermal-magnetic release, undervoltage release, IP40 front.","salesMarkdown":"The Siemens 3VA1096-2ED36-0DA0 is a SENTRON 3VA molded case circuit breaker (MCCB) rated 16 A continuous at 40 °C, with a TM210 thermal-magnetic overcurrent release and an integrated undervoltage release (UVR). The 16 A rating holds flat across 40–55 °C ambient, then derates to 15 A at 60–70 °C — so in a warm panel near the top of a cabinet, you lose 1 A of headroom, not the whole rating. Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, and 7.5 kA at 690 V, which covers most industrial distribution panels for fault-current coordination downstream of a transformer. Three-pole construction, IP40 on the front face — rated for indoor panel mounting where the enclosure provides the environmental seal. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a compact 3-pole MCCB footprint that fits standard Siemens 3VA panel cutouts and busbar systems. The TM210 release is fixed thermal-magnetic, not electronic, so no auxiliary power supply needed for the trip unit; the undervoltage release (UVR) does require a separate control voltage connection.","metaTitle":"Siemens 3VA1096-2ED36-0DA0 SENTRON MCCB, 16 A, 3-Pole, 52.5","metaDescription":"Siemens 3VA1096-2ED36-0DA0 SENTRON molded case circuit breaker, 16 A rated, 3-pole, 52.5 kA breaking at 240 V. TM210 release, undervoltage release. Active production, available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Undervoltage Release":"Yes","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10962ED360AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1507629&mlfb=3VA1096-2ED36-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED36-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1096-2ED36-0DA0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time figure is published here."},{"question":"What is the breaking capacity of 3VA1096-2ED36-0DA0 at different voltages?","answer":"52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V."},{"question":"Does the 3VA1096-2ED36-0DA0 include an undervoltage release?","answer":"Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release, which trips the breaker on loss of control voltage."},{"question":"What is the ambient temperature derating for this MCCB?","answer":"Rated 16 A from 40 °C to 55 °C, then derates to 15 A at 60 °C through 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-2ED36-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-2ED36-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}