{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-2ED42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-2ED42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-2ED42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1096-2ED42-0AA0, molded case circuit breaker, 4-pole, 16 A (Iu), TM210 thermal-magnetic release, line protection version, breaking capacity 52.5 kA at 240 V AC.","salesMarkdown":"Its continuous current rating Iu is 16 A, and it holds that rating flat from 40 °C through 55 °C; at 60 °C it derates to 15 A, and at 70 °C it still delivers 15 A — useful when the breaker sits in a warm enclosure near other heat sources. The TM210 overcurrent release combines a thermal element for overload protection and a magnetic element for short-circuit protection. The 210 designation indicates a fixed thermal rating with an adjustable magnetic trip range (typically 5–10x In for this family), letting you dial in the instantaneous pickup to coordinate with downstream devices. ## Breaking capacity across voltages — selectivity headroom This MCCB delivers 52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. The steep drop above 415 V reflects the physics of arc extinction in air; at 690 V the 7.5 kA figure still covers most industrial motor-drive branch circuits. ## Panel integration — dimensions and mounting The breaker measures 101.6 mm wide, 130 mm high, and 70 mm deep — a 4-pole footprint that fits standard SENTRON 3VA panel cutouts and busbar systems. Front IP40 protects against tool entry in the enclosure; the rear and sides are protected by the panel itself.","metaTitle":"Siemens 3VA1096-2ED42-0AA0 SENTRON MCCB, 4P, 16 A, TM210","metaDescription":"Siemens SENTRON 3VA1096-2ED42-0AA0 molded case circuit breaker, 4-pole, 16 A rated at 40 °C, TM210 release, breaking capacity 52.5 kA at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"4","Width":"101.6 mm","Height":"130 mm","Product Status":"Active","Insulation Voltage Ui":"800 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/07bfde06ff7c7d93fb406ab34cee4041.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=776&mlfb=3VA1096-2ED42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-2ED42-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-2ED42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-2ED42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}