{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-3ED32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-3ED32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-3ED32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-3ED32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1096-3ED32-0KH0, 3-pole molded case circuit breaker, 16 A rated continuous current (Iu), TM210 thermal-magnetic overcurrent release, shunt trip (STL), breaking capacity 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, 7.5 kA at 690 V.","salesMarkdown":"## 16 A SENTRON MCCB with shunt trip — panel-fit specs and thermal limits At 240 V it interrupts 75.6 kA; at 415 V that drops to 52.5 kA; at 440 V it's 32 kA; at 690 V it's 7.5 kA. For a 16 A frame those are strong numbers — it'll handle high-fault service-entrance or distribution panels, not just downstream subfeeds. It holds a full 16 A from 40 °C up to 50 °C, then steps down: 15.36 A at 55 °C, 15.04 A at 60 °C, 14.72 A at 65 °C, and 14.4 A at 70 °C. If your panel hits 60 °C regularly, you're giving up about an amp. ## Mounting and integration — DIN-rail footprint and IP40 front The 3VA1096-3ED32-0KH0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard SENTRON 3VA footprint that clips onto DIN rail. The integrated shunt trip release is listed as order code 3VA9688-0BL33 — that's the factory-fit accessory inside this variant.","metaTitle":"Siemens 3VA1096-3ED32-0KH0 SENTRON MCCB, 16 A, 3-pole, 75.6","metaDescription":"Siemens SENTRON 3VA1096-3ED32-0KH0 molded case circuit breaker, 16 A rated, 3-pole, TM210 trip, shunt trip release. Breaking capacity 75.6 kA at 240 V. Current production. Availabl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"15.36 A","at 60 °C":"15.04 A","at 65 °C":"14.72 A","at 70 °C":"14.4 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"16 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"16 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"16 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=95587&mlfb=3VA1096-3ED32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-3ED32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1096-3ED32-0KH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is 3VA1096-3ED32-0KH0's listed depth and width?","answer":"Depth is 70 mm, width is 76.2 mm, height is 130 mm — a standard SENTRON 3VA DIN-rail footprint."},{"question":"What compliance documentation does this brand provide for 3VA1096-3ED32-0KH0?","answer":"As a Siemens SENTRON product, this MCCB carries the usual CE, UL, and IEC certifications typical for the 3VA series. Specific documentation (RoHS, REACH, UL file number) is available upon request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-3ED32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-3ED32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}