{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-4ED32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-4ED32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-4ED32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-4ED32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1096-4ED32-0AH0, molded case circuit breaker, 3-pole, 16 A, TM210 thermal-magnetic release, 121 kA at 240 V, 75.6 kA at 415 V, 70 mm depth.","salesMarkdown":"The TM210 thermal-magnetic release provides fixed overload and short-circuit protection — no adjustable trip curve, which simplifies specification but locks you into the factory calibration. Breaking capacity hits 121 kA at 240 V and 75.6 kA at 415 V, so it handles high-fault-current panels without cascading upstream. Thermal derating is minimal through 50 °C — still rated 16 A — then drops gradually to 14.4 A at 70 °C. For a panel running warm near the top of the enclosure, you lose about 1.6 A off the nameplate; plan the load accordingly if ambient exceeds 55 °C.","metaTitle":"Siemens SENTRON 3VA1096-4ED32-0AH0 MCCB, 16 A, 121 kA at 240","metaDescription":"Siemens SENTRON 3VA1096-4ED32-0AH0 molded case circuit breaker, 16 A rated, 3-pole, TM210 release. Breaking capacity 121 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 690 V":"11.9 kA","at 40 °C":"16 A","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"15.36 A","at 60 °C":"15.04 A","at 65 °C":"14.72 A","at 70 °C":"14.4 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"16 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"16 A","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Adjustable response value current / lr min.":"16 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=436959&mlfb=3VA1096-4ED32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-4ED32-0AH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1096-4ED32-0AH0?","answer":"Submit an RFQ through this listing. We source the part to order and confirm availability and current pricing at quote time."},{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"75.6 kA at 415 V, which covers most industrial distribution panels with high available fault current."},{"question":"What is the depth of 3VA1096-4ED32-0AH0?","answer":"70 mm depth, plus the standard DIN-rail mounting depth."},{"question":"What is the width of 3VA1096-4ED32-0AH0?","answer":"76.2 mm width — three-pole footprint, fits standard SENTRON 3VA panel cutouts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-4ED32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-4ED32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}